Product Identification


Identification


Product


Dec start address Hex start address Type Size Lock level Locked fcts Unlocked fcts
50000 0xC350 Info 69 NONE READ READ

Dec address Hex address Words count Description Unit Data type
50000 0xC350 4 "SOCO" - STRING_16
50004 0xC354 1 Product order ID (Countis:100, Protection:200, Atys:300, Diris:400) - U16
50005 0xC355 1 Product ID (EX: 1000 ATS3) - U16
50006 0xC356 1 MODBUS Table Version - U16
50007 0xC357 1 Product software version (EX: 100 Version 1.00) - U16
50008 0xC358 1 Serial_AA_SS - U16_HEX
50009 0xC359 1 Serial_SST_L - U16_HEX
50010 0xC35A 1 Serial_order - U16
50011 0xC35B 2 Serial_Reserve - U32
50013 0xC35D 4 See "Code table" tab for more details - U64_HEX
50017 0xC361 1 Customization data loaded (True/False) - U8
50018 0xC362 1 Product version (Major) - U16
50019 0xC363 1 Product version (Minor) - U16
50020 0xC364 1 Product version (Revision) - U16
50021 0xC365 1 Product version (Build) - U16
50022 0xC366 3 Product build date - DATETIME_3
50025 0xC369 1 Software technical base version (Major) - U16
50026 0xC36A 1 Software technical base version (Minor) - U16
50027 0xC36B 1 Software technical base version (Revision) - U16
50028 0xC36C 1 Customization version (Major) - U16
50029 0xC36D 1 Customization version (Minor) - U16
50030 0xC36E 4 Product VLO (EX : "880100") - STRING_NORM
50034 0xC372 4 Customization VLO (EX : "880700") - STRING_NORM
50038 0xC376 4 Software technical base VLO (EX : "880600") - STRING_NORM
50042 0xC37A 8 Vendor name (EX : "SOCOMEC") - STRING_NORM
50050 0xC382 8 Product name (EX : "PMD EE") - STRING_NORM
50058 0xC38A 8 Extended name - STRING_NORM
50066 0xC392 1 Resource version (Build 2) - U16
50067 0xC393 2 Net ID - U32_HEX

Identification by blinking LED


Dec start address Hex start address Type Size Lock level Locked fcts Unlocked fcts
57864 0xE208 Commands 1 NONE WRITE WRITE

Dec address Hex address Words count Description Unit Data type
57864 0xE208 1 Action
1 : Start blinking
- U16



Visualization


ATS Status


Status


Dec start address Hex start address Type Size Lock level Locked fcts Unlocked fcts
20480 0x5000 Info 15 NONE READ READ

Dec address Hex address Words count Description Unit Data type
20480 0x5000 2 Date & Time Current - DATETIME
20482 0x5002 1 Operating Mode
0x0010 : Auto Mode
0x0020 : Manu Mode
0x0040 : Inhibit Mode
- U16_HEX
20483 0x5003 1 Switch Position
0 : Unknown
1 : Position 0
2 : Position 1
3 : Position 2
- U8
20484 0x5004 1 Source 1 Start Generator relay State
0 : Not active
1 : Active
- U8
20485 0x5005 1 Source 2 Start Generator relay State
0 : Not Active
1 : Active
- U8
20486 0x5006 1 Priority
0 : Network
1 : Source 1
2 : Source 2
- U8
20487 0x5007 1 Source1 State
0 : Under Threshold BusBar
1 : Present
2 : Available
- U8
20488 0x5008 1 Source2 State
0 : Under Threshold BusBar
1 : Present
2 : Available
- U8
20489 0x5009 1 Test in progress
0x0000 : None
0x0001 : TOF
0x0002 : EOF
0x0004 : TON
0x0008 : EON
- U16_HEX
20490 0x500A 1 Alarm / Fault summary
0 : None
1 : Alarm
2 : Fault
3 : Alarm + Fault
- U8
20491 0x500B 1 Active Fault (with highest priority)
0 : None
1 : Unexpected Transfer
2 : Failed to Transfer
3 : Operating Factor Fault
4 : Max PWD Attempts
5 : Genset Failed to Start
6 : External Fault
- U16
20492 0x500C 1 Last Switch over cause
0 : None
1 : Manual
2 : Remote controlled
3 : Under voltage source 1
4 : Under voltage source 2
5 : Over voltage source 1
6 : Over voltage source 2
7 : Under Frequence source 1
8 : Under Frequence source 2
9 : Over Frequence source 1
10 : Over Frequence source 2
11 : Unbalance Source 1
12 : Unbalance Source 2
13 : Rotation Source 1
14 : Rotation Source 2
- U8
20493 0x500D 1 Product is available
0 : Not available
1 : Available
- U8
20494 0x500E 1 Source Inhibition state
0 : No inhibition
1 : S1 Inhibited
2 : S2 Inhibited
3 : Both source inhibited
- U8

Timer state


Dec start address Hex start address Type Size Lock level Locked fcts Unlocked fcts
21248 0x5300 Info 36 NONE READ READ

Dec address Hex address Words count Description Unit Data type
21248 0x5300 2 Date & Time Current s DATETIME
21250 0x5302 1 1FT Source1 Failure Timer s 10⁻¹ U16
21251 0x5303 1 1RT Source1 Available/Return Timer s U16
21252 0x5304 1 1CT Source1 Genset Cooldown timer s U16
21253 0x5305 1 Reserved - -
21254 0x5306 1 1ST Source1 Start TimeOut timer s U16
21255 0x5307 1 2FT Source2 Failure Timer s 10⁻¹ U16
21256 0x5308 1 2RT Source2 Available/Return Timer s U16
21257 0x5309 1 2CT Source2 Genset Cooldown timer s U16
21258 0x530A 1 Reserved - -
21259 0x530B 1 2ST Source2 Start TimeOut timer s U16
21260 0x530C 1 DBT Dead Band timer s U16
21261 0x530D 1 Reserved - -
21262 0x530E 1 Limit_TOT Test on load is limited
0 : unlimited
1 : limited
- U8
21263 0x530F 1 TOT Test on load duration timer s U16
21264 0x5310 1 T3T Test on load end timer s U16
21265 0x5311 1 Limit_TFT Test off load is limited
0 : unlimited
1 : limited
- U8
21266 0x5312 1 TFT Test off load duration timer s U16
21267 0x5313 1 E1T Time before external order on load s U16
21268 0x5314 1 E3T Time after external order on load s U16
21269 0x5315 1 Limit_E2T External order on load is limited
0 : unlimited
1 : limited
- U8
21270 0x5316 1 E2T External order on load duration s U16
21271 0x5317 1 E5T Time before external order off load s U16
21272 0x5318 1 E7T Time after external order off load s U16
21273 0x5319 1 Limit_E6T External order off load is limited
0 : unlimited
1 : limited
- U8
21274 0x531A 1 E6T External order off load duration s U16
21275 0x531B 1 Reserved - -
21276 0x531C 1 Reserved - -
21277 0x531D 1 Reserved - -
21278 0x531E 1 Reserved - -
21279 0x531F 1 Reserved - -
21280 0x5320 1 Reserved - -
21281 0x5321 1 Reserved - -
21282 0x5322 1 Reserved - -
21283 0x5323 1 Reserved - -


Measure


Network


Network Inst Source #1


Dec start address Hex start address Type Size Lock level Locked fcts Unlocked fcts
36864 0x9000 Info 37 NONE READ READ

Dec address Hex address Words count Description Unit Data type
36864 0x9000 2 Date of last instance s DATETIME
36866 0x9002 1 Integration time s / 5 U16
36867 0x9003 2 System Ph-N Voltage V 10⁻² U32
36869 0x9005 2 System Ph-Ph Voltage V 10⁻² U32
36871 0x9007 2 Frequency mHz U32
36873 0x9009 2 Ph-N Voltage : V1 V 10⁻² U32
36875 0x900B 2 Ph-N Voltage : V2 V 10⁻² U32
36877 0x900D 2 Ph-N Voltage : V3 V 10⁻² U32
36879 0x900F 2 Ph-N Voltage : Vn V 10⁻² U32
36881 0x9011 2 Ph-Ph Voltage : U12 V 10⁻² U32
36883 0x9013 2 Ph-Ph Voltage : U23 V 10⁻² U32
36885 0x9015 2 Ph-Ph Voltage : U31 V 10⁻² U32
36887 0x9017 2 Vdir V 10⁻² U32
36889 0x9019 2 Vinv V 10⁻² U32
36891 0x901B 2 Vhom V 10⁻² U32
36893 0x901D 1 Vnb % / 100 U16
36894 0x901E 2 Udir V 10⁻² U32
36896 0x9020 2 Uinv V 10⁻² U32
36898 0x9022 1 Unb % / 100 U16
36899 0x9023 1 Vnba % / 100 U16
36900 0x9024 1 Unba % / 100 U16

Network Inst Source #2


Dec start address Hex start address Type Size Lock level Locked fcts Unlocked fcts
36908 0x902C Info 37 NONE READ READ

Dec address Hex address Words count Description Unit Data type
36908 0x902C 2 Date of last instance s DATETIME
36910 0x902E 1 Integration time s / 5 U16
36911 0x902F 2 System Ph-N Voltage V 10⁻² U32
36913 0x9031 2 System Ph-Ph Voltage V 10⁻² U32
36915 0x9033 2 Frequency mHz U32
36917 0x9035 2 Ph-N Voltage : V1 V 10⁻² U32
36919 0x9037 2 Ph-N Voltage : V2 V 10⁻² U32
36921 0x9039 2 Ph-N Voltage : V3 V 10⁻² U32
36923 0x903B 2 Ph-N Voltage : Vn V 10⁻² U32
36925 0x903D 2 Ph-Ph Voltage : U12 V 10⁻² U32
36927 0x903F 2 Ph-Ph Voltage : U23 V 10⁻² U32
36929 0x9041 2 Ph-Ph Voltage : U31 V 10⁻² U32
36931 0x9043 2 Vdir V 10⁻² U32
36933 0x9045 2 Vinv V 10⁻² U32
36935 0x9047 2 Vhom V 10⁻² U32
36937 0x9049 1 Vnb % / 100 U16
36938 0x904A 2 Udir V 10⁻² U32
36940 0x904C 2 Uinv V 10⁻² U32
36942 0x904E 1 Unb % / 100 U16
36943 0x904F 1 Vnba % / 100 U16
36944 0x9050 1 Unba % / 100 U16

Network Inst. Fundamental Source #1


Dec start address Hex start address Type Size Lock level Locked fcts Unlocked fcts
37120 0x9100 Info 24 NONE READ READ

Dec address Hex address Words count Description Unit Data type
37120 0x9100 2 Date of last instance s DATETIME
37122 0x9102 1 Integration time s / 5 U16
37123 0x9103 2 Ph-N voltage: V1h1 V 10⁻² U32
37125 0x9105 2 Ph-N voltage: V2h1 V 10⁻² U32
37127 0x9107 2 Ph-N voltage: V3h1 V 10⁻² U32
37129 0x9109 2 Ph-N voltage: Vnh1 V 10⁻² U32
37131 0x910B 1 Ph-N voltage phase: phV1h1 ? / 10 S16
37132 0x910C 1 Ph-N voltage phase: phV2h1 ? / 10 S16
37133 0x910D 1 Ph-N voltage phase: phV3h1 ? / 10 S16
37134 0x910E 1 Ph-N voltage phase: phVnh1 ? / 10 S16
37135 0x910F 2 Ph-Ph voltage: U12h1 V 10⁻² U32
37137 0x9111 2 Ph-Ph voltage: U23h1 V 10⁻² U32
37139 0x9113 2 Ph-Ph voltage: U31h1 V 10⁻² U32
37141 0x9115 1 Ph-Ph voltage phase: phU12h1 ? / 10 S16
37142 0x9116 1 Ph-Ph voltage phase: phU23h1 ? / 10 S16
37143 0x9117 1 Ph-Ph voltage phase: phU31h1 ? / 10 S16

Network Inst. Fundamental Source #2


Dec start address Hex start address Type Size Lock level Locked fcts Unlocked fcts
37296 0x91B0 Info 24 NONE READ READ

Dec address Hex address Words count Description Unit Data type
37296 0x91B0 2 Date of last instance s DATETIME
37298 0x91B2 1 Integration time s / 5 U16
37299 0x91B3 2 Ph-N voltage: V1h1 V 10⁻² U32
37301 0x91B5 2 Ph-N voltage: V2h1 V 10⁻² U32
37303 0x91B7 2 Ph-N voltage: V3h1 V 10⁻² U32
37305 0x91B9 2 Ph-N voltage: Vnh1 V 10⁻² U32
37307 0x91BB 1 Ph-N voltage phase: phV1h1 ? / 10 S16
37308 0x91BC 1 Ph-N voltage phase: phV2h1 ? / 10 S16
37309 0x91BD 1 Ph-N voltage phase: phV3h1 ? / 10 S16
37310 0x91BE 1 Ph-N voltage phase: phVnh1 ? / 10 S16
37311 0x91BF 2 Ph-Ph voltage: U12h1 V 10⁻² U32
37313 0x91C1 2 Ph-Ph voltage: U23h1 V 10⁻² U32
37315 0x91C3 2 Ph-Ph voltage: U31h1 V 10⁻² U32
37317 0x91C5 1 Ph-Ph voltage phase: phU12h1 ? / 10 S16
37318 0x91C6 1 Ph-Ph voltage phase: phU23h1 ? / 10 S16
37319 0x91C7 1 Ph-Ph voltage phase: phU31h1 ? / 10 S16



Input Output


Logical Input #1


Dec start address Hex start address Type Size Lock level Locked fcts Unlocked fcts
11520 0x2D00 Info 2 NONE READ READ

Dec address Hex address Words count Description Unit Data type
11520 0x2D00 1 Input function
0 : --- - None
4 : ALO - Alarm Logical In
5 : AACK - Alarm Aknoledge
21 : INH - Inhibition
22 : INHP - Partial Inhibition
23 : INHT - Total Inhibition
24 : TON - Test on load
25 : TOF - Test off load
26 : EON - External order on load
27 : EOF - External order off load
28 : MRT - Manual Retransfer
29 : PRI - Change Priority
30 : SS1 - Validation Stabilization source 1
31 : SS2 - Validation Stabilization source 2
32 : ALE - External Alarm
33 : FTE - External Fault
36 : MSR - Priority test on load
37 : OA1 - Override source 1 available
38 : OA2 - Override source 2 available
39 : OU1 - Override source 1 unavailable
40 : OU2 - Override source 2 unavailable
41 : RST - Reset faults state
43 : AC1 - Switch position 1
44 : AC2 - Switch position 2
45 : AC0 - Switch position 0
46 : AC0A - Switch A position 0
47 : AC0B - Switch B position 0
48 : MAN - RTSE in manual mode
49 : LCK - RTSE locked
50 : CHP - Change Position
53 : PS1 - Go to position 1
54 : PS2 - Go to position 2
55 : PS0 - Go to position 0
57 : BLK - Interlocking blocked
58 : TP1 - Trip S1
59 : TP2 - Trip S2
61 : EST - Emergency Stop
64 : BCT - Bypass Current Timer
255 : eFctMultiple
- U8
11521 0x2D01 1 Input State
0 : Deactivated
1 : Activated
- U8

Logical Input #2


Dec start address Hex start address Type Size Lock level Locked fcts Unlocked fcts
11522 0x2D02 Info 2 NONE READ READ

Dec address Hex address Words count Description Unit Data type
11522 0x2D02 1 Input function
0 : --- - None
4 : ALO - Alarm Logical In
5 : AACK - Alarm Aknoledge
21 : INH - Inhibition
22 : INHP - Partial Inhibition
23 : INHT - Total Inhibition
24 : TON - Test on load
25 : TOF - Test off load
26 : EON - External order on load
27 : EOF - External order off load
28 : MRT - Manual Retransfer
29 : PRI - Change Priority
30 : SS1 - Validation Stabilization source 1
31 : SS2 - Validation Stabilization source 2
32 : ALE - External Alarm
33 : FTE - External Fault
36 : MSR - Priority test on load
37 : OA1 - Override source 1 available
38 : OA2 - Override source 2 available
39 : OU1 - Override source 1 unavailable
40 : OU2 - Override source 2 unavailable
41 : RST - Reset faults state
43 : AC1 - Switch position 1
44 : AC2 - Switch position 2
45 : AC0 - Switch position 0
46 : AC0A - Switch A position 0
47 : AC0B - Switch B position 0
48 : MAN - RTSE in manual mode
49 : LCK - RTSE locked
50 : CHP - Change Position
53 : PS1 - Go to position 1
54 : PS2 - Go to position 2
55 : PS0 - Go to position 0
57 : BLK - Interlocking blocked
58 : TP1 - Trip S1
59 : TP2 - Trip S2
61 : EST - Emergency Stop
64 : BCT - Bypass Current Timer
255 : eFctMultiple
- U8
11523 0x2D03 1 Input State
0 : Deactivated
1 : Activated
- U8

Logical Input #3


Dec start address Hex start address Type Size Lock level Locked fcts Unlocked fcts
11524 0x2D04 Info 2 NONE READ READ

Dec address Hex address Words count Description Unit Data type
11524 0x2D04 1 Input function
0 : --- - None
4 : ALO - Alarm Logical In
5 : AACK - Alarm Aknoledge
21 : INH - Inhibition
22 : INHP - Partial Inhibition
23 : INHT - Total Inhibition
24 : TON - Test on load
25 : TOF - Test off load
26 : EON - External order on load
27 : EOF - External order off load
28 : MRT - Manual Retransfer
29 : PRI - Change Priority
30 : SS1 - Validation Stabilization source 1
31 : SS2 - Validation Stabilization source 2
32 : ALE - External Alarm
33 : FTE - External Fault
36 : MSR - Priority test on load
37 : OA1 - Override source 1 available
38 : OA2 - Override source 2 available
39 : OU1 - Override source 1 unavailable
40 : OU2 - Override source 2 unavailable
41 : RST - Reset faults state
43 : AC1 - Switch position 1
44 : AC2 - Switch position 2
45 : AC0 - Switch position 0
46 : AC0A - Switch A position 0
47 : AC0B - Switch B position 0
48 : MAN - RTSE in manual mode
49 : LCK - RTSE locked
50 : CHP - Change Position
53 : PS1 - Go to position 1
54 : PS2 - Go to position 2
55 : PS0 - Go to position 0
57 : BLK - Interlocking blocked
58 : TP1 - Trip S1
59 : TP2 - Trip S2
61 : EST - Emergency Stop
64 : BCT - Bypass Current Timer
255 : eFctMultiple
- U8
11525 0x2D05 1 Input State
0 : Deactivated
1 : Activated
- U8

Logical Input #4


Dec start address Hex start address Type Size Lock level Locked fcts Unlocked fcts
11526 0x2D06 Info 2 NONE READ READ

Dec address Hex address Words count Description Unit Data type
11526 0x2D06 1 Input function
0 : --- - None
4 : ALO - Alarm Logical In
5 : AACK - Alarm Aknoledge
21 : INH - Inhibition
22 : INHP - Partial Inhibition
23 : INHT - Total Inhibition
24 : TON - Test on load
25 : TOF - Test off load
26 : EON - External order on load
27 : EOF - External order off load
28 : MRT - Manual Retransfer
29 : PRI - Change Priority
30 : SS1 - Validation Stabilization source 1
31 : SS2 - Validation Stabilization source 2
32 : ALE - External Alarm
33 : FTE - External Fault
36 : MSR - Priority test on load
37 : OA1 - Override source 1 available
38 : OA2 - Override source 2 available
39 : OU1 - Override source 1 unavailable
40 : OU2 - Override source 2 unavailable
41 : RST - Reset faults state
43 : AC1 - Switch position 1
44 : AC2 - Switch position 2
45 : AC0 - Switch position 0
46 : AC0A - Switch A position 0
47 : AC0B - Switch B position 0
48 : MAN - RTSE in manual mode
49 : LCK - RTSE locked
50 : CHP - Change Position
53 : PS1 - Go to position 1
54 : PS2 - Go to position 2
55 : PS0 - Go to position 0
57 : BLK - Interlocking blocked
58 : TP1 - Trip S1
59 : TP2 - Trip S2
61 : EST - Emergency Stop
64 : BCT - Bypass Current Timer
255 : eFctMultiple
- U8
11527 0x2D07 1 Input State
0 : Deactivated
1 : Activated
- U8

Logical Input #5


Dec start address Hex start address Type Size Lock level Locked fcts Unlocked fcts
11528 0x2D08 Info 2 NONE READ READ

Dec address Hex address Words count Description Unit Data type
11528 0x2D08 1 Input function
0 : --- - None
4 : ALO - Alarm Logical In
5 : AACK - Alarm Aknoledge
21 : INH - Inhibition
22 : INHP - Partial Inhibition
23 : INHT - Total Inhibition
24 : TON - Test on load
25 : TOF - Test off load
26 : EON - External order on load
27 : EOF - External order off load
28 : MRT - Manual Retransfer
29 : PRI - Change Priority
30 : SS1 - Validation Stabilization source 1
31 : SS2 - Validation Stabilization source 2
32 : ALE - External Alarm
33 : FTE - External Fault
36 : MSR - Priority test on load
37 : OA1 - Override source 1 available
38 : OA2 - Override source 2 available
39 : OU1 - Override source 1 unavailable
40 : OU2 - Override source 2 unavailable
41 : RST - Reset faults state
43 : AC1 - Switch position 1
44 : AC2 - Switch position 2
45 : AC0 - Switch position 0
46 : AC0A - Switch A position 0
47 : AC0B - Switch B position 0
48 : MAN - RTSE in manual mode
49 : LCK - RTSE locked
50 : CHP - Change Position
53 : PS1 - Go to position 1
54 : PS2 - Go to position 2
55 : PS0 - Go to position 0
57 : BLK - Interlocking blocked
58 : TP1 - Trip S1
59 : TP2 - Trip S2
61 : EST - Emergency Stop
64 : BCT - Bypass Current Timer
255 : eFctMultiple
- U8
11529 0x2D09 1 Input State
0 : Deactivated
1 : Activated
- U8

Logical Input #6


Dec start address Hex start address Type Size Lock level Locked fcts Unlocked fcts
11530 0x2D0A Info 2 NONE READ READ

Dec address Hex address Words count Description Unit Data type
11530 0x2D0A 1 Input function
0 : --- - None
4 : ALO - Alarm Logical In
5 : AACK - Alarm Aknoledge
21 : INH - Inhibition
22 : INHP - Partial Inhibition
23 : INHT - Total Inhibition
24 : TON - Test on load
25 : TOF - Test off load
26 : EON - External order on load
27 : EOF - External order off load
28 : MRT - Manual Retransfer
29 : PRI - Change Priority
30 : SS1 - Validation Stabilization source 1
31 : SS2 - Validation Stabilization source 2
32 : ALE - External Alarm
33 : FTE - External Fault
36 : MSR - Priority test on load
37 : OA1 - Override source 1 available
38 : OA2 - Override source 2 available
39 : OU1 - Override source 1 unavailable
40 : OU2 - Override source 2 unavailable
41 : RST - Reset faults state
43 : AC1 - Switch position 1
44 : AC2 - Switch position 2
45 : AC0 - Switch position 0
46 : AC0A - Switch A position 0
47 : AC0B - Switch B position 0
48 : MAN - RTSE in manual mode
49 : LCK - RTSE locked
50 : CHP - Change Position
53 : PS1 - Go to position 1
54 : PS2 - Go to position 2
55 : PS0 - Go to position 0
57 : BLK - Interlocking blocked
58 : TP1 - Trip S1
59 : TP2 - Trip S2
61 : EST - Emergency Stop
64 : BCT - Bypass Current Timer
255 : eFctMultiple
- U8
11531 0x2D0B 1 Input State
0 : Deactivated
1 : Activated
- U8

Logical Inputs All


Dec start address Hex start address Type Size Lock level Locked fcts Unlocked fcts
11248 0x2BF0 Info 7 NONE READ READ

Dec address Hex address Words count Description Unit Data type
11248 0x2BF0 1 Inputs number - U16
11249 0x2BF1 2 Bit x : Input x Available (1)/Not available (0) - U32_HEX
11251 0x2BF3 2 Bit x : Input x Activated (1)/Deactivated (0) - U32_HEX
11253 0x2BF5 2 Bit x : Input x NC (1)/NO (0) - U32_HEX

Logical Output (start gen) #1


Dec start address Hex start address Type Size Lock level Locked fcts Unlocked fcts
11600 0x2D50 Info 2 NONE READ READ

Dec address Hex address Words count Description Unit Data type
11600 0x2D50 1 Output function
0 : --- - None
6 : ARO - Alarm Report Output
75 : GS1 - Genset Source 1 start
76 : GS2 - Genset Source 2 start
77 : S1A - Source 1 available
78 : S2A - Source 2 available
79 : SCA - At Least 1 source avail
80 : S1U - Source 1 unavailable
81 : S2U - Source 2 unavailable
82 : AC1 - Source 1 closed
83 : AC2 - Source 2 closed
84 : AC0 - Off Position
88 : FLT - Faults active
94 : ROS - TON or EON in progress
109 : AUD - Critical Alarm Active
255 : eFctMultiple
- U8
11601 0x2D51 1 Output State
0 : Deactivated
1 : Activated
- U8

Logical Output (start gen) #2


Dec start address Hex start address Type Size Lock level Locked fcts Unlocked fcts
11616 0x2D60 Info 2 NONE READ READ

Dec address Hex address Words count Description Unit Data type
11616 0x2D60 1 Output function
0 : --- - None
6 : ARO - Alarm Report Output
75 : GS1 - Genset Source 1 start
76 : GS2 - Genset Source 2 start
77 : S1A - Source 1 available
78 : S2A - Source 2 available
79 : SCA - At Least 1 source avail
80 : S1U - Source 1 unavailable
81 : S2U - Source 2 unavailable
82 : AC1 - Source 1 closed
83 : AC2 - Source 2 closed
84 : AC0 - Off Position
88 : FLT - Faults active
94 : ROS - TON or EON in progress
109 : AUD - Critical Alarm Active
255 : eFctMultiple
- U8
11617 0x2D61 1 Output State
0 : Deactivated
1 : Activated
- U8

Logical Output (start gen) #3


Dec start address Hex start address Type Size Lock level Locked fcts Unlocked fcts
11632 0x2D70 Info 2 NONE READ READ

Dec address Hex address Words count Description Unit Data type
11632 0x2D70 1 Output function
0 : --- - None
6 : ARO - Alarm Report Output
75 : GS1 - Genset Source 1 start
76 : GS2 - Genset Source 2 start
77 : S1A - Source 1 available
78 : S2A - Source 2 available
79 : SCA - At Least 1 source avail
80 : S1U - Source 1 unavailable
81 : S2U - Source 2 unavailable
82 : AC1 - Source 1 closed
83 : AC2 - Source 2 closed
84 : AC0 - Off Position
88 : FLT - Faults active
94 : ROS - TON or EON in progress
109 : AUD - Critical Alarm Active
255 : eFctMultiple
- U8
11633 0x2D71 1 Output State
0 : Deactivated
1 : Activated
- U8

Logical Output (start gen) #4


Dec start address Hex start address Type Size Lock level Locked fcts Unlocked fcts
11648 0x2D80 Info 2 NONE READ READ

Dec address Hex address Words count Description Unit Data type
11648 0x2D80 1 Output function
0 : --- - None
6 : ARO - Alarm Report Output
75 : GS1 - Genset Source 1 start
76 : GS2 - Genset Source 2 start
77 : S1A - Source 1 available
78 : S2A - Source 2 available
79 : SCA - At Least 1 source avail
80 : S1U - Source 1 unavailable
81 : S2U - Source 2 unavailable
82 : AC1 - Source 1 closed
83 : AC2 - Source 2 closed
84 : AC0 - Off Position
88 : FLT - Faults active
94 : ROS - TON or EON in progress
109 : AUD - Critical Alarm Active
255 : eFctMultiple
- U8
11649 0x2D81 1 Output State
0 : Deactivated
1 : Activated
- U8

Logical Outputs All


Dec start address Hex start address Type Size Lock level Locked fcts Unlocked fcts
11280 0x2C10 Info 7 NONE READ READ

Dec address Hex address Words count Description Unit Data type
11280 0x2C10 1 Outputs number - U16
11281 0x2C11 2 Bit x : Output x Available (1)/Not available (0) - U32_HEX
11283 0x2C13 2 Bit x : Output x Activated (1)/Deactivated (0) - U32_HEX
11285 0x2C15 2 Bit x : Output x NC (1)/NO (0) - U32_HEX

Relay informations #1


Dec start address Hex start address Type Size Lock level Locked fcts Unlocked fcts
16464 0x4050 Info 2 NONE READ READ

Dec address Hex address Words count Description Unit Data type
16464 0x4050 1 Output Relay function
0 : --- - None
6 : ARO - Alarm Report Output
70 : PO1 - Switch to pos 1
71 : PO2 - Switch to pos 2
72 : PO0 - Switch to pos 0
73 : PA0 - Switch A to pos 0 (S1)
74 : PB0 - Switch B to pos 0 (S2)
77 : S1A - Source 1 available
78 : S2A - Source 2 available
79 : SCA - At Least 1 source avail
80 : S1U - Source 1 unavailable
81 : S2U - Source 2 unavailable
82 : AC1 - Source 1 closed
83 : AC2 - Source 2 closed
84 : AC0 - Off Position
88 : FLT - Faults active
94 : ROS - TON or EON in progress
109 : AUD - Critical Alarm Active
255 : eFctMultiple
- U8
16465 0x4051 1 Output Relay State
0 : Deactivated
1 : Activated
- U8

Relay informations #2


Dec start address Hex start address Type Size Lock level Locked fcts Unlocked fcts
16472 0x4058 Info 2 NONE READ READ

Dec address Hex address Words count Description Unit Data type
16472 0x4058 1 Output Relay function
0 : --- - None
6 : ARO - Alarm Report Output
70 : PO1 - Switch to pos 1
71 : PO2 - Switch to pos 2
72 : PO0 - Switch to pos 0
73 : PA0 - Switch A to pos 0 (S1)
74 : PB0 - Switch B to pos 0 (S2)
77 : S1A - Source 1 available
78 : S2A - Source 2 available
79 : SCA - At Least 1 source avail
80 : S1U - Source 1 unavailable
81 : S2U - Source 2 unavailable
82 : AC1 - Source 1 closed
83 : AC2 - Source 2 closed
84 : AC0 - Off Position
88 : FLT - Faults active
94 : ROS - TON or EON in progress
109 : AUD - Critical Alarm Active
255 : eFctMultiple
- U8
16473 0x4059 1 Output Relay State
0 : Deactivated
1 : Activated
- U8

Relay informations #3


Dec start address Hex start address Type Size Lock level Locked fcts Unlocked fcts
16480 0x4060 Info 2 NONE READ READ

Dec address Hex address Words count Description Unit Data type
16480 0x4060 1 Output Relay function
0 : --- - None
6 : ARO - Alarm Report Output
70 : PO1 - Switch to pos 1
71 : PO2 - Switch to pos 2
72 : PO0 - Switch to pos 0
73 : PA0 - Switch A to pos 0 (S1)
74 : PB0 - Switch B to pos 0 (S2)
77 : S1A - Source 1 available
78 : S2A - Source 2 available
79 : SCA - At Least 1 source avail
80 : S1U - Source 1 unavailable
81 : S2U - Source 2 unavailable
82 : AC1 - Source 1 closed
83 : AC2 - Source 2 closed
84 : AC0 - Off Position
88 : FLT - Faults active
94 : ROS - TON or EON in progress
109 : AUD - Critical Alarm Active
255 : eFctMultiple
- U8
16481 0x4061 1 Output Relay State
0 : Deactivated
1 : Activated
- U8

Relay informations #4


Dec start address Hex start address Type Size Lock level Locked fcts Unlocked fcts
16488 0x4068 Info 2 NONE READ READ

Dec address Hex address Words count Description Unit Data type
16488 0x4068 1 Output Relay function
0 : --- - None
6 : ARO - Alarm Report Output
70 : PO1 - Switch to pos 1
71 : PO2 - Switch to pos 2
72 : PO0 - Switch to pos 0
73 : PA0 - Switch A to pos 0 (S1)
74 : PB0 - Switch B to pos 0 (S2)
77 : S1A - Source 1 available
78 : S2A - Source 2 available
79 : SCA - At Least 1 source avail
80 : S1U - Source 1 unavailable
81 : S2U - Source 2 unavailable
82 : AC1 - Source 1 closed
83 : AC2 - Source 2 closed
84 : AC0 - Off Position
88 : FLT - Faults active
94 : ROS - TON or EON in progress
109 : AUD - Critical Alarm Active
255 : eFctMultiple
- U8
16489 0x4069 1 Output Relay State
0 : Deactivated
1 : Activated
- U8


Statistics


Operating hours counters


Dec start address Hex start address Type Size Lock level Locked fcts Unlocked fcts
512 0x0200 Info 4 NONE READ READ

Dec address Hex address Words count Description Unit Data type
512 0x0200 2 Total operating hours counter s U32
514 0x0202 2 Partial operating hours counter s U32

Product Time meters


Dec start address Hex start address Type Size Lock level Locked fcts Unlocked fcts
23296 0x5B00 Info 30 NONE READ READ

Dec address Hex address Words count Description Unit Data type
23296 0x5B00 2 Total time in position 1 s U32
23298 0x5B02 2 User partial time in position 1 s U32
23300 0x5B04 2 Time in position 1 since last commutation s U32
23302 0x5B06 2 Total time load supplied by source 1 s U32
23304 0x5B08 2 Total time in position 2 s U32
23306 0x5B0A 2 User partial time in position 2 s U32
23308 0x5B0C 2 Time in position 2 since last commutation s U32
23310 0x5B0E 2 Total time load supplied by source 2 s U32
23312 0x5B10 2 Start order active duration Genset source 1 s U32
23314 0x5B12 2 Start order active duration Genset source 2 s U32
23316 0x5B14 1 Start order activation counter Genset source 1 - U16
23317 0x5B15 1 Start order activation counter Genset source 2 - U16
23318 0x5B16 2 Engine Run Time Source 1 s U32
23320 0x5B18 2 Engine Run Time - On Load - Source 1 s U32
23322 0x5B1A 2 Engine Run Time Source 2 s U32
23324 0x5B1C 2 Engine Run Time - On Load - Source 2 s U32

Switch counters


Dec start address Hex start address Type Size Lock level Locked fcts Unlocked fcts
23552 0x5C00 Info 15 NONE READ READ

Dec address Hex address Words count Description Unit Data type
23552 0x5C00 2 Switch Operating hours counter s U32
23554 0x5C02 1 Total Cycles counter - U16
23555 0x5C03 1 Cycles in auto mode - U16
23556 0x5C04 1 Cycles in remote control mode - U16
23557 0x5C05 1 Total switches counter - U16
23558 0x5C06 1 Total Position 0 switches counter - U16
23559 0x5C07 1 Total Position 1 switches counter - U16
23560 0x5C08 1 Total Position 2 switches counter - U16
23561 0x5C09 1 Position 0 switches in auto mode counter - U16
23562 0x5C0A 1 Position 1 switches in auto mode counter - U16
23563 0x5C0B 1 Position 2 switches in auto mode counter - U16
23564 0x5C0C 1 Position 0 switches in control mode counter - U16
23565 0x5C0D 1 Position 1 switches in control mode counter - U16
23566 0x5C0E 1 Position 2 switches in control mode counter - U16


Diagnostic


Source NetCnx computed #1


Dec start address Hex start address Type Size Lock level Locked fcts Unlocked fcts
12320 0x3020 Info 9 NONE READ READ

Dec address Hex address Words count Description Unit Data type
12320 0x3020 1 Computed : Network connection type
0 : Not computed
1 : 1P + N
2 : 2P
3 : 2P + N
4 : 3P
5 : 3P + N
- U8
12321 0x3021 2 Computed : Nominal Voltage V U32
12323 0x3023 1 Computed : Nominal Frequency
0 : 50 Hz - eDefFnom_50Hz
1 : 60 Hz - eDefFnom_60Hz
2 : NU - Error
- U8
12324 0x3024 1 Computed : Phase rotation
0 : V1 - V2 - V3
1 : V1 - V3 - V2
- U8
12325 0x3025 1 Diagnosticated : Network connection type
0 : Not Diagnosticated
1 : NOK
2 : OK
- U8
12326 0x3026 1 Diagnosticated : Nominal Voltage
0 : Not Diagnosticated
1 : NOK
2 : OK
- U8
12327 0x3027 1 Diagnosticated : Nominal Frequency
0 : Not Diagnosticated
1 : NOK
2 : OK
- U8
12328 0x3028 1 Diagnosticated : Phase rotation
0 : Not Diagnosticated
1 : NOK
2 : OK
- U8

Source NetCnx computed #2


Dec start address Hex start address Type Size Lock level Locked fcts Unlocked fcts
12330 0x302A Info 9 NONE READ READ

Dec address Hex address Words count Description Unit Data type
12330 0x302A 1 Computed : Network connection type
0 : Not computed
1 : 1P + N
2 : 2P
3 : 2P + N
4 : 3P
5 : 3P + N
- U8
12331 0x302B 2 Computed : Nominal Voltage V U32
12333 0x302D 1 Computed : Nominal Frequency
0 : 50 Hz - eDefFnom_50Hz
1 : 60 Hz - eDefFnom_60Hz
2 : NU - Error
- U8
12334 0x302E 1 Computed : Phase rotation
0 : V1 - V2 - V3
1 : V1 - V3 - V2
- U8
12335 0x302F 1 Diagnosticated : Network connection type
0 : Not Diagnosticated
1 : NOK
2 : OK
- U8
12336 0x3030 1 Diagnosticated : Nominal Voltage
0 : Not Diagnosticated
1 : NOK
2 : OK
- U8
12337 0x3031 1 Diagnosticated : Nominal Frequency
0 : Not Diagnosticated
1 : NOK
2 : OK
- U8
12338 0x3032 1 Diagnosticated : Phase rotation
0 : Not Diagnosticated
1 : NOK
2 : OK
- U8

Modbus diag


Dec start address Hex start address Type Size Lock level Locked fcts Unlocked fcts
880 0x0370 Info 8 NONE READ READ

Dec address Hex address Words count Description Unit Data type
880 0x0370 2 RS SlaveRxRequestCnt - U32
882 0x0372 2 RS SlaveTxRequestCnt - U32
884 0x0374 2 RS SlaveErrorCnt - U32

Modbus diag reset


Dec start address Hex start address Type Size Lock level Locked fcts Unlocked fcts
879 0x036F Commands 1 USER NONE WRITE

Dec address Hex address Words count Description Unit Data type
879 0x036F 1 Modbus diag reset
0 : No action
1 : Reset statistics
- U16


Log


Events log


Command

Dec start address Hex start address Type Size Lock level Locked fcts Unlocked fcts
4720 0x1270 Command 1 NONE WRITE_MANY WRITE_MANY

Dec address Hex address Words count Description Unit Data type
4720 0x1270 1 Start record number (0 to 65534) or 65535 for last record - U16

Header

Dec start address Hex start address Type Size Lock level Locked fcts Unlocked fcts
4736 0x1280 Header 3 NONE READ READ

Dec address Hex address Words count Description Unit Data type
4736 0x1280 1 Next record number - U16
4737 0x1281 1 Items count (max 3 per request) - U16
4738 0x1282 1 Item size (words) - U16

Data

Dec start address Hex start address Type Size Lock level Locked fcts Unlocked fcts
4739 0x1283 Data 8 NONE READ READ

Dec address Hex address Words count Description Unit Data type
4739 0x1283 1 Event ID
0x1102 : BET in default
0x1103 : BET not present
0x1105 : StartGen relay fault
0x2001 : Source 1 Lost
0x2002 : Source 1 comes back
0x2003 : Source 1 not started (1ST / 2ST)
0x2004 : Source 1 Undervoltage
0x2005 : Source 1 Overvoltage
0x2006 : Source 1 Unbalanced
0x2007 : Source 1 Underfrequency
0x2008 : Source 1 Overfrequency
0x2009 : Source 1 Rotation fault
0x200A : Source 1 Neutral fault
0x200B : External fault with zero return source 1
0x200C : External fault without zero return source 1
0x200D : Source 1 Overload
0x200E : Source 1 Inhibit Start
0x200F : Source 1 Inhibit Stop
0x2101 : Source 2 Lost
0x2102 : Source 2 comes back
0x2103 : Source 2 not started (1ST / 2ST)
0x2104 : Source 2 Undervoltage
0x2105 : Source 2 Overvoltage
0x2106 : Source 2 Unbalanced
0x2107 : Source 2 Underfrequency
0x2108 : Source 2 Overfrequency
0x2109 : Source 2 Rotation fault
0x210A : Source 2 Neutral fault
0x210B : External fault with zero return source 2
0x210C : External fault without zero return source 2
0x210D : Source 2 Overload
0x210E : Source 2 Inhibit Start
0x210F : Source 2 Inhibit Stop
0x2201 : Test on load start
0x2202 : Test on load end
0x2203 : Test on load failed
0x2204 : Test off load start
0x2205 : Test off load end
0x2206 : Test off load failed
0x2207 : External order on load start
0x2208 : External order on load end
0x2209 : External order on load failed
0x220A : External order off load start
0x220B : External order off load end
0x220C : External order off load failed
0x220D : Battery charger start
0x220E : Battery charger end
0x220F : Unlimited TOF/TOL stopped because of communication timeout
0x2301 : Automatic switch to position 0
0x2302 : Automatic switch to position 1
0x2303 : Automatic switch to position 2
0x2304 : Manual switch to position 0
0x2305 : Manual switch to position 1
0x2306 : Manual switch to position 2
0x2307 : Remote controlled switch to position 0
0x2308 : Remote controlled switch to position 1
0x2309 : Remote controlled switch to position 2
0x230A : Operating Factor Fault
0x230B : Position 0 not reached
0x230C : Position 1 not reached
0x230D : Position 2 not reached
0x230E : Unexpected switch to pos 0 when in auto mode
0x230F : Unexpected switch to pos 1 when in auto mode
0x2310 : Unexpected switch to pos 2 when in auto mode
0x2311 : Unexpected switch to pos 0 when in locked mode
0x2312 : Unexpected switch to pos 1 when in locked mode
0x2313 : Unexpected switch to pos 2 when in locked mode
0x2314 : In Phase Transfer Bypassed
0x2315 : In Phase Transfer Inhibited
0x2316 : In Phase Transfer Start
0x2317 : In Phase Transfer End
0x2401 : Input/Output configuration changed
0x2402 : Application/Timers configuration changed
0x2403 : Sources (thresholds) configuration changed
0x2404 : Communication configuration changed
0x2405 : HMI configuration changed
0x2406 : Network configuration changed
0x2409 : Default configuration loaded
0x240F : Config Change Failed
0x2410 : Password Changed
0x2412 : Load Config Changed
0x2413 : Exerciser Config Changed
0x2414 : Timer Config Changed
0x2415 : Alarm Config Changed
0x2501 : 1FT - Primary Source fail timer start
0x251D : 1FT - Primary Source fail timer
0x2502 : 1AT/1RT - Primary Source availability/return timer start
0x251E : 1AT/1RT - Primary Source availability/return timer stop
0x2503 : 1CT - Primary Source cooldown timer start
0x251F : 1CT - Primary Source cooldown timer stop
0x2504 : 10T - Primary Source return to 0 timer start
0x2520 : 10T - Primary Source return to 0 timer stop
0x2505 : 1ST - Primary Source wait for start timer start
0x2521 : 1ST - Primary Source wait for start timer stop
0x2506 : 1EET - Primary Source battery charger timeout start
0x2522 : 1EET - Primary Source battery charger timeout stop
0x2507 : 1EDT - Primary Source battery charger duration start
0x2523 : 1EDT - Primary Source battery charger duration stop
0x2508 : 2FT - Secondary Source fail timer start
0x2524 : 2FT - Secondary Source fail timer stop
0x2509 : 2AT/2RT - Secondary Source availability/return timer start
0x2525 : 2AT/2RT - Secondary Source availability/return timer stop
0x250A : 2CT - Secondary Source cooldown timer start
0x2526 : 2CT - Secondary Source cooldown timer stop
0x250B : 20T - Secondary Source return to 0 timer start
0x2527 : 20T - Secondary Source return to 0 timer stop
0x250C : 2ST - Secondary Source wait for start timer start
0x2528 : 2ST - Secondary Source wait for start timer stop
0x250D : 2EET - Secondary Source battery charger timeout start
0x2529 : 2EET - Secondary Source battery charger timeout stop
0x250E : 2EDT - Secondary Source battery charger duration start
0x252A : 2EDT - Secondary Source battery charger duration stop
0x250F : DBT - Dead band timer start
0x252B : DBT - Dead band timer stop
0x2510 : TOL - Test on load duration timer start
0x252C : TOL - Test on load duration timer stop
0x2511 : T3T - Test on load end timer start
0x252D : T3T - Test on load end timer stop
0x2512 : TOF - Test off load duration timer start
0x252E : TOF - Test off load duration timer stop
0x2513 : E1T - Time before external order on load start
0x252F : E1T - Time before external order on load stop
0x2514 : E3T - Time after external order on load start
0x2530 : E3T - Time after external order on load stop
0x2515 : E2T - External order on load duration start
0x2531 : E2T - External order on load duration stop
0x2516 : E5T - Time before external order off load start
0x2532 : E5T - Time before external order off load stop
0x2517 : E7T - Time after external order off load start
0x2533 : E7T - Time after external order off load stop
0x2518 : E6T - External order off load duration start
0x2534 : E6T - External order off load duration stop
0x2519 : LSD - LoadShedding_On Timer start
0x2535 : LSD - LoadShedding_On Timer stop
0x251A : LSR - LoadShedding_Off Timer start
0x2536 : LSR - LoadShedding_Off Timer stop
0x251C : StartGen idle timer start
0x2538 : StartGen idle timer stop
0x2601 : Switched to auto mode
0x2602 : Switched to manual mode
0x2603 : Switched to locked mode
0x2604 : Switched to control mode
0x2605 : Retransfer validated
0x2606 : Test off load validated
0x2607 : Alarms / Faults reset
0x2608 : Product becomes available
0x2609 : Product becomes unavailable
0x260A : Product becomes inhibited
0x260B : Product no more inhibited
0x2706 : Source 1 Time meter reset
0x270C : Source 2 Time meter reset
0x270D : Start order count reset
0x270E : Start order active duration reset
0x270F : Secondary source duration reset
0x2710 : Secondary source active duration reset
0x2711 : Source 1 load supplied duration reset
0x2712 : Source 2 load supplied duration reset
0x2713 : Cycle Counter Reset
0x2714 : Partial Position Timer Meter Counter Reset
0x2715 : Operating Hours Counter Reset
0x2716 : Genset Stats Reset
0x2801 : Load shedding request activated
0x2802 : Load shedding request deactivated
0x2803 : Elevator activated
0x2804 : Elevator deactivated
0x2901 : Exerciser 1 Started
0x2902 : Exerciser 1 Stopped
0x2903 : Exerciser 2 Started
0x2904 : Exerciser 2 Stopped
0x2905 : Exerciser 3 Started
0x2906 : Exerciser 3 Stopped
0x2907 : Exerciser 4 Started
0x2908 : Exerciser 4 Stopped
0x4002 : Alarm Log Cleared
0x4003 : Event Log Cleared
0x4100 : Context Load Failed
0x4101 : Context Save Failed
0x4200 : Inspection Took Place
0x4201 : Passwords Reset
0x4202 : Phone Number Changed
0x4203 : Open Door
0x4204 : Product Padlocked
0x4205 : Interlock Failed
0x8000 : Power On
0x8001 : Power Off
0x8100 : Configuration changed
0x8101 : Configuration save failed
0x8102 : Configuration load failed
0x8105 : Configuration date saved
0x8106 : Configuration date save failed
0x8107 : Configuration date read failed
0x8110 : Configuration calibration read failed
0x8200 : Total Energy meters set
0x8201 : Partial Energy meters reset
0x8300 : User reset
0x8301 : Watchdog reset
0x8305 : Hard Reset
0x8306 : Device Reboot
- U16_HEX
4740 0x1284 2 Start Date s DATETIME
4742 0x1286 1 Cause - U16_HEX
4743 0x1287 1 Status
0 : Active
1 : Finished
- U16
4744 0x1288 1 Reserved U16 - S16
4745 0x1289 2 Reserved U32 - S32

Alarming


Analog-Maintenance


ALM Ana Maint Current Status #1


Dec start address Hex start address Type Size Lock level Locked fcts Unlocked fcts
5029 0x13A5 Info 23 NONE READ READ

Dec address Hex address Words count Description Unit Data type
5029 0x13A5 1 Ack ID - U16
5030 0x13A6 1 Status
0 : Inactive
1 : Active
2 : Finished
3 : FinishedAndAck
- U8
5031 0x13A7 1 Alarm cause :
0 : Cause Unknown
1 : Analog. High Th. Single
2 : Analog. High Th. Tri. And
3 : Analog. High Th. Tri. Or
4 : Analog. Low Th Single
5 : Analog. Low Th. Tri. And
6 : Analog. Low Th. Tri. Or
19 : Maintenance
- U8
5032 0x13A8 1 Criticality :
0 : Information
1 : Warning
2 : Critical
- U8
5033 0x13A9 2 Start date - DATETIME
5035 0x13AB 2 Duration s U32
5037 0x13AD 2 Analog variable (ServiceID)
5206 : Total Cycle Counter
5415 : Total Switch Counter
5434 : Genset S1 Activation Time
5435 : Genset S2 Activation Time
5436 : Genset S1 On Load Time
5437 : Genset S2 On Load Time
156094 : Time Since Last Inspection
- U32
5039 0x13AF 1 Analog variable (Instance index) - U16
5040 0x13B0 1 Analog variable (Instance type) - U16
5041 0x13B1 1 Startup delay s / 2 U16
5042 0x13B2 1 Dropout delay s / 2 U16
5043 0x13B3 1 Hysteresis % / 10 U16
5044 0x13B4 4 Threshold - S64
5048 0x13B8 4 Min/Max - S64

ALM Ana Maint Current Status #2


Dec start address Hex start address Type Size Lock level Locked fcts Unlocked fcts
5053 0x13BD Info 23 NONE READ READ

Dec address Hex address Words count Description Unit Data type
5053 0x13BD 1 Ack ID - U16
5054 0x13BE 1 Status
0 : Inactive
1 : Active
2 : Finished
3 : FinishedAndAck
- U8
5055 0x13BF 1 Alarm cause :
0 : Cause Unknown
1 : Analog. High Th. Single
2 : Analog. High Th. Tri. And
3 : Analog. High Th. Tri. Or
4 : Analog. Low Th Single
5 : Analog. Low Th. Tri. And
6 : Analog. Low Th. Tri. Or
19 : Maintenance
- U8
5056 0x13C0 1 Criticality :
0 : Information
1 : Warning
2 : Critical
- U8
5057 0x13C1 2 Start date - DATETIME
5059 0x13C3 2 Duration s U32
5061 0x13C5 2 Analog variable (ServiceID)
5206 : Total Cycle Counter
5415 : Total Switch Counter
5434 : Genset S1 Activation Time
5435 : Genset S2 Activation Time
5436 : Genset S1 On Load Time
5437 : Genset S2 On Load Time
156094 : Time Since Last Inspection
- U32
5063 0x13C7 1 Analog variable (Instance index) - U16
5064 0x13C8 1 Analog variable (Instance type) - U16
5065 0x13C9 1 Startup delay s / 2 U16
5066 0x13CA 1 Dropout delay s / 2 U16
5067 0x13CB 1 Hysteresis % / 10 U16
5068 0x13CC 4 Threshold - S64
5072 0x13D0 4 Min/Max - S64

ALM Ana Maint Current Status #3


Dec start address Hex start address Type Size Lock level Locked fcts Unlocked fcts
5077 0x13D5 Info 23 NONE READ READ

Dec address Hex address Words count Description Unit Data type
5077 0x13D5 1 Ack ID - U16
5078 0x13D6 1 Status
0 : Inactive
1 : Active
2 : Finished
3 : FinishedAndAck
- U8
5079 0x13D7 1 Alarm cause :
0 : Cause Unknown
1 : Analog. High Th. Single
2 : Analog. High Th. Tri. And
3 : Analog. High Th. Tri. Or
4 : Analog. Low Th Single
5 : Analog. Low Th. Tri. And
6 : Analog. Low Th. Tri. Or
19 : Maintenance
- U8
5080 0x13D8 1 Criticality :
0 : Information
1 : Warning
2 : Critical
- U8
5081 0x13D9 2 Start date - DATETIME
5083 0x13DB 2 Duration s U32
5085 0x13DD 2 Analog variable (ServiceID)
5206 : Total Cycle Counter
5415 : Total Switch Counter
5434 : Genset S1 Activation Time
5435 : Genset S2 Activation Time
5436 : Genset S1 On Load Time
5437 : Genset S2 On Load Time
156094 : Time Since Last Inspection
- U32
5087 0x13DF 1 Analog variable (Instance index) - U16
5088 0x13E0 1 Analog variable (Instance type) - U16
5089 0x13E1 1 Startup delay s / 2 U16
5090 0x13E2 1 Dropout delay s / 2 U16
5091 0x13E3 1 Hysteresis % / 10 U16
5092 0x13E4 4 Threshold - S64
5096 0x13E8 4 Min/Max - S64

ALM Ana Maint Current Status #4


Dec start address Hex start address Type Size Lock level Locked fcts Unlocked fcts
5101 0x13ED Info 23 NONE READ READ

Dec address Hex address Words count Description Unit Data type
5101 0x13ED 1 Ack ID - U16
5102 0x13EE 1 Status
0 : Inactive
1 : Active
2 : Finished
3 : FinishedAndAck
- U8
5103 0x13EF 1 Alarm cause :
0 : Cause Unknown
1 : Analog. High Th. Single
2 : Analog. High Th. Tri. And
3 : Analog. High Th. Tri. Or
4 : Analog. Low Th Single
5 : Analog. Low Th. Tri. And
6 : Analog. Low Th. Tri. Or
19 : Maintenance
- U8
5104 0x13F0 1 Criticality :
0 : Information
1 : Warning
2 : Critical
- U8
5105 0x13F1 2 Start date - DATETIME
5107 0x13F3 2 Duration s U32
5109 0x13F5 2 Analog variable (ServiceID)
5206 : Total Cycle Counter
5415 : Total Switch Counter
5434 : Genset S1 Activation Time
5435 : Genset S2 Activation Time
5436 : Genset S1 On Load Time
5437 : Genset S2 On Load Time
156094 : Time Since Last Inspection
- U32
5111 0x13F7 1 Analog variable (Instance index) - U16
5112 0x13F8 1 Analog variable (Instance type) - U16
5113 0x13F9 1 Startup delay s / 2 U16
5114 0x13FA 1 Dropout delay s / 2 U16
5115 0x13FB 1 Hysteresis % / 10 U16
5116 0x13FC 4 Threshold - S64
5120 0x1400 4 Min/Max - S64

ALM Ana Maint Current Status #5


Dec start address Hex start address Type Size Lock level Locked fcts Unlocked fcts
5125 0x1405 Info 23 NONE READ READ

Dec address Hex address Words count Description Unit Data type
5125 0x1405 1 Ack ID - U16
5126 0x1406 1 Status
0 : Inactive
1 : Active
2 : Finished
3 : FinishedAndAck
- U8
5127 0x1407 1 Alarm cause :
0 : Cause Unknown
1 : Analog. High Th. Single
2 : Analog. High Th. Tri. And
3 : Analog. High Th. Tri. Or
4 : Analog. Low Th Single
5 : Analog. Low Th. Tri. And
6 : Analog. Low Th. Tri. Or
19 : Maintenance
- U8
5128 0x1408 1 Criticality :
0 : Information
1 : Warning
2 : Critical
- U8
5129 0x1409 2 Start date - DATETIME
5131 0x140B 2 Duration s U32
5133 0x140D 2 Analog variable (ServiceID)
5206 : Total Cycle Counter
5415 : Total Switch Counter
5434 : Genset S1 Activation Time
5435 : Genset S2 Activation Time
5436 : Genset S1 On Load Time
5437 : Genset S2 On Load Time
156094 : Time Since Last Inspection
- U32
5135 0x140F 1 Analog variable (Instance index) - U16
5136 0x1410 1 Analog variable (Instance type) - U16
5137 0x1411 1 Startup delay s / 2 U16
5138 0x1412 1 Dropout delay s / 2 U16
5139 0x1413 1 Hysteresis % / 10 U16
5140 0x1414 4 Threshold - S64
5144 0x1418 4 Min/Max - S64

ALM Ana Maint Current Status #6


Dec start address Hex start address Type Size Lock level Locked fcts Unlocked fcts
5149 0x141D Info 23 NONE READ READ

Dec address Hex address Words count Description Unit Data type
5149 0x141D 1 Ack ID - U16
5150 0x141E 1 Status
0 : Inactive
1 : Active
2 : Finished
3 : FinishedAndAck
- U8
5151 0x141F 1 Alarm cause :
0 : Cause Unknown
1 : Analog. High Th. Single
2 : Analog. High Th. Tri. And
3 : Analog. High Th. Tri. Or
4 : Analog. Low Th Single
5 : Analog. Low Th. Tri. And
6 : Analog. Low Th. Tri. Or
19 : Maintenance
- U8
5152 0x1420 1 Criticality :
0 : Information
1 : Warning
2 : Critical
- U8
5153 0x1421 2 Start date - DATETIME
5155 0x1423 2 Duration s U32
5157 0x1425 2 Analog variable (ServiceID)
5206 : Total Cycle Counter
5415 : Total Switch Counter
5434 : Genset S1 Activation Time
5435 : Genset S2 Activation Time
5436 : Genset S1 On Load Time
5437 : Genset S2 On Load Time
156094 : Time Since Last Inspection
- U32
5159 0x1427 1 Analog variable (Instance index) - U16
5160 0x1428 1 Analog variable (Instance type) - U16
5161 0x1429 1 Startup delay s / 2 U16
5162 0x142A 1 Dropout delay s / 2 U16
5163 0x142B 1 Hysteresis % / 10 U16
5164 0x142C 4 Threshold - S64
5168 0x1430 4 Min/Max - S64


Logical


ALM Log Current Status #1


Dec start address Hex start address Type Size Lock level Locked fcts Unlocked fcts
5456 0x1550 Info 11 NONE READ READ

Dec address Hex address Words count Description Unit Data type
5456 0x1550 1 Ack ID - U16
5457 0x1551 1 Status :
0 : Inactive
1 : Active
2 : Finished
3 : FinishedAndAck
- U8
5458 0x1552 1 Alarm cause :
0 : Cause Unknown
7 : Logical Active
- U8
5459 0x1553 1 Criticality :
0 : Information
1 : Warning
2 : Critical
- U8
5460 0x1554 2 Start date - DATETIME
5462 0x1556 2 Duration s U32
5464 0x1558 1 Logical input
0 : Input 1
1 : Input 2
2 : Input 3
3 : Input 4
4 : Input 5
5 : Input 6
255 : Not used
- U8
5465 0x1559 1 Startup delay s / 2 U16
5466 0x155A 1 Dropout delay s / 2 U16

ALM Log Current Status #2


Dec start address Hex start address Type Size Lock level Locked fcts Unlocked fcts
5467 0x155B Info 11 NONE READ READ

Dec address Hex address Words count Description Unit Data type
5467 0x155B 1 Ack ID - U16
5468 0x155C 1 Status :
0 : Inactive
1 : Active
2 : Finished
3 : FinishedAndAck
- U8
5469 0x155D 1 Alarm cause :
0 : Cause Unknown
7 : Logical Active
- U8
5470 0x155E 1 Criticality :
0 : Information
1 : Warning
2 : Critical
- U8
5471 0x155F 2 Start date - DATETIME
5473 0x1561 2 Duration s U32
5475 0x1563 1 Logical input
0 : Input 1
1 : Input 2
2 : Input 3
3 : Input 4
4 : Input 5
5 : Input 6
255 : Not used
- U8
5476 0x1564 1 Startup delay s / 2 U16
5477 0x1565 1 Dropout delay s / 2 U16

ALM Log Current Status #3


Dec start address Hex start address Type Size Lock level Locked fcts Unlocked fcts
5478 0x1566 Info 11 NONE READ READ

Dec address Hex address Words count Description Unit Data type
5478 0x1566 1 Ack ID - U16
5479 0x1567 1 Status :
0 : Inactive
1 : Active
2 : Finished
3 : FinishedAndAck
- U8
5480 0x1568 1 Alarm cause :
0 : Cause Unknown
7 : Logical Active
- U8
5481 0x1569 1 Criticality :
0 : Information
1 : Warning
2 : Critical
- U8
5482 0x156A 2 Start date - DATETIME
5484 0x156C 2 Duration s U32
5486 0x156E 1 Logical input
0 : Input 1
1 : Input 2
2 : Input 3
3 : Input 4
4 : Input 5
5 : Input 6
255 : Not used
- U8
5487 0x156F 1 Startup delay s / 2 U16
5488 0x1570 1 Dropout delay s / 2 U16

ALM Log Current Status #4


Dec start address Hex start address Type Size Lock level Locked fcts Unlocked fcts
5489 0x1571 Info 11 NONE READ READ

Dec address Hex address Words count Description Unit Data type
5489 0x1571 1 Ack ID - U16
5490 0x1572 1 Status :
0 : Inactive
1 : Active
2 : Finished
3 : FinishedAndAck
- U8
5491 0x1573 1 Alarm cause :
0 : Cause Unknown
7 : Logical Active
- U8
5492 0x1574 1 Criticality :
0 : Information
1 : Warning
2 : Critical
- U8
5493 0x1575 2 Start date - DATETIME
5495 0x1577 2 Duration s U32
5497 0x1579 1 Logical input
0 : Input 1
1 : Input 2
2 : Input 3
3 : Input 4
4 : Input 5
5 : Input 6
255 : Not used
- U8
5498 0x157A 1 Startup delay s / 2 U16
5499 0x157B 1 Dropout delay s / 2 U16


System


ALM Sys Current Status #1


Dec start address Hex start address Type Size Lock level Locked fcts Unlocked fcts
6400 0x1900 Info 23 NONE READ READ

Dec address Hex address Words count Description Unit Data type
6400 0x1900 1 Ack ID - U16
6401 0x1901 1 Status :
0 : Inactive
1 : Active
2 : Finished
3 : FinishedAndAck
- U8
6402 0x1902 1 Alarm Type
0 : None
1 : Net Rotation
20 : External Alarm
21 : I/O Connection Failure
22 : Controller Unavailable
23 : Load Not Supplied
9 : RTC Low Battery
24 : DC Aux. Supply Out Of Bounds
- U8
6403 0x1903 1 Alarm cause :
0 : Cause Unknown
12 : System Active
- U8
6404 0x1904 1 Criticality :
0 : Information
1 : Warning
2 : Critical
- U8
6405 0x1905 2 Start date - DATETIME
6407 0x1907 2 Duration s U32
6409 0x1909 1 Startup delay s / 2 U16
6410 0x190A 1 Dropout delay s / 2 U16
6411 0x190B 2 SpeData 1 - U32
6413 0x190D 1 SpeData 5 - U16
6414 0x190E 1 SpeData 6 - U16
6415 0x190F 4 SpeData 7 - S64
6419 0x1913 4 SpeData 8 - S64

ALM Sys Current Status #2


Dec start address Hex start address Type Size Lock level Locked fcts Unlocked fcts
6423 0x1917 Info 23 NONE READ READ

Dec address Hex address Words count Description Unit Data type
6423 0x1917 1 Ack ID - U16
6424 0x1918 1 Status :
0 : Inactive
1 : Active
2 : Finished
3 : FinishedAndAck
- U8
6425 0x1919 1 Alarm Type
0 : None
1 : Net Rotation
20 : External Alarm
21 : I/O Connection Failure
22 : Controller Unavailable
23 : Load Not Supplied
9 : RTC Low Battery
24 : DC Aux. Supply Out Of Bounds
- U8
6426 0x191A 1 Alarm cause :
0 : Cause Unknown
12 : System Active
- U8
6427 0x191B 1 Criticality :
0 : Information
1 : Warning
2 : Critical
- U8
6428 0x191C 2 Start date - DATETIME
6430 0x191E 2 Duration s U32
6432 0x1920 1 Startup delay s / 2 U16
6433 0x1921 1 Dropout delay s / 2 U16
6434 0x1922 2 SpeData 1 - U32
6436 0x1924 1 SpeData 5 - U16
6437 0x1925 1 SpeData 6 - U16
6438 0x1926 4 SpeData 7 - S64
6442 0x192A 4 SpeData 8 - S64

ALM Sys Current Status #3


Dec start address Hex start address Type Size Lock level Locked fcts Unlocked fcts
6446 0x192E Info 23 NONE READ READ

Dec address Hex address Words count Description Unit Data type
6446 0x192E 1 Ack ID - U16
6447 0x192F 1 Status :
0 : Inactive
1 : Active
2 : Finished
3 : FinishedAndAck
- U8
6448 0x1930 1 Alarm Type
0 : None
1 : Net Rotation
20 : External Alarm
21 : I/O Connection Failure
22 : Controller Unavailable
23 : Load Not Supplied
9 : RTC Low Battery
24 : DC Aux. Supply Out Of Bounds
- U8
6449 0x1931 1 Alarm cause :
0 : Cause Unknown
12 : System Active
- U8
6450 0x1932 1 Criticality :
0 : Information
1 : Warning
2 : Critical
- U8
6451 0x1933 2 Start date - DATETIME
6453 0x1935 2 Duration s U32
6455 0x1937 1 Startup delay s / 2 U16
6456 0x1938 1 Dropout delay s / 2 U16
6457 0x1939 2 SpeData 1 - U32
6459 0x193B 1 SpeData 5 - U16
6460 0x193C 1 SpeData 6 - U16
6461 0x193D 4 SpeData 7 - S64
6465 0x1941 4 SpeData 8 - S64

ALM Sys Current Status #4


Dec start address Hex start address Type Size Lock level Locked fcts Unlocked fcts
6469 0x1945 Info 23 NONE READ READ

Dec address Hex address Words count Description Unit Data type
6469 0x1945 1 Ack ID - U16
6470 0x1946 1 Status :
0 : Inactive
1 : Active
2 : Finished
3 : FinishedAndAck
- U8
6471 0x1947 1 Alarm Type
0 : None
1 : Net Rotation
20 : External Alarm
21 : I/O Connection Failure
22 : Controller Unavailable
23 : Load Not Supplied
9 : RTC Low Battery
24 : DC Aux. Supply Out Of Bounds
- U8
6472 0x1948 1 Alarm cause :
0 : Cause Unknown
12 : System Active
- U8
6473 0x1949 1 Criticality :
0 : Information
1 : Warning
2 : Critical
- U8
6474 0x194A 2 Start date - DATETIME
6476 0x194C 2 Duration s U32
6478 0x194E 1 Startup delay s / 2 U16
6479 0x194F 1 Dropout delay s / 2 U16
6480 0x1950 2 SpeData 1 - U32
6482 0x1952 1 SpeData 5 - U16
6483 0x1953 1 SpeData 6 - U16
6484 0x1954 4 SpeData 7 - S64
6488 0x1958 4 SpeData 8 - S64

ALM Sys Current Status #5


Dec start address Hex start address Type Size Lock level Locked fcts Unlocked fcts
6492 0x195C Info 23 NONE READ READ

Dec address Hex address Words count Description Unit Data type
6492 0x195C 1 Ack ID - U16
6493 0x195D 1 Status :
0 : Inactive
1 : Active
2 : Finished
3 : FinishedAndAck
- U8
6494 0x195E 1 Alarm Type
0 : None
1 : Net Rotation
20 : External Alarm
21 : I/O Connection Failure
22 : Controller Unavailable
23 : Load Not Supplied
9 : RTC Low Battery
24 : DC Aux. Supply Out Of Bounds
- U8
6495 0x195F 1 Alarm cause :
0 : Cause Unknown
12 : System Active
- U8
6496 0x1960 1 Criticality :
0 : Information
1 : Warning
2 : Critical
- U8
6497 0x1961 2 Start date - DATETIME
6499 0x1963 2 Duration s U32
6501 0x1965 1 Startup delay s / 2 U16
6502 0x1966 1 Dropout delay s / 2 U16
6503 0x1967 2 SpeData 1 - U32
6505 0x1969 1 SpeData 5 - U16
6506 0x196A 1 SpeData 6 - U16
6507 0x196B 4 SpeData 7 - S64
6511 0x196F 4 SpeData 8 - S64

ALM Sys Current Status #6


Dec start address Hex start address Type Size Lock level Locked fcts Unlocked fcts
6515 0x1973 Info 23 NONE READ READ

Dec address Hex address Words count Description Unit Data type
6515 0x1973 1 Ack ID - U16
6516 0x1974 1 Status :
0 : Inactive
1 : Active
2 : Finished
3 : FinishedAndAck
- U8
6517 0x1975 1 Alarm Type
0 : None
1 : Net Rotation
20 : External Alarm
21 : I/O Connection Failure
22 : Controller Unavailable
23 : Load Not Supplied
9 : RTC Low Battery
24 : DC Aux. Supply Out Of Bounds
- U8
6518 0x1976 1 Alarm cause :
0 : Cause Unknown
12 : System Active
- U8
6519 0x1977 1 Criticality :
0 : Information
1 : Warning
2 : Critical
- U8
6520 0x1978 2 Start date - DATETIME
6522 0x197A 2 Duration s U32
6524 0x197C 1 Startup delay s / 2 U16
6525 0x197D 1 Dropout delay s / 2 U16
6526 0x197E 2 SpeData 1 - U32
6528 0x1980 1 SpeData 5 - U16
6529 0x1981 1 SpeData 6 - U16
6530 0x1982 4 SpeData 7 - S64
6534 0x1986 4 SpeData 8 - S64


Faults


ALM Fault Current Status #1


Dec start address Hex start address Type Size Lock level Locked fcts Unlocked fcts
5952 0x1740 Info 9 NONE READ READ

Dec address Hex address Words count Description Unit Data type
5952 0x1740 1 Ack ID - U16
5953 0x1741 1 Status :
0 : Inactive
1 : Active
2 : Finished
3 : FinishedAndAck
- U8
5954 0x1742 1 Alarm Type
0 : None
1 : Unexpected Transfer
2 : Failed to Transfer
3 : Operating Factor Fault
4 : Max PWD Attempts
5 : Genset Failed to Start
6 : External Fault
- U8
5955 0x1743 1 Alarm cause :
0 : Cause Unknown
20 : Fault Active
- U8
5956 0x1744 1 Criticality :
0 : Information
1 : Warning
2 : Critical
- U8
5957 0x1745 2 Start date - DATETIME
5959 0x1747 2 Duration s U32

ALM Fault Current Status #2


Dec start address Hex start address Type Size Lock level Locked fcts Unlocked fcts
5975 0x1757 Info 9 NONE READ READ

Dec address Hex address Words count Description Unit Data type
5975 0x1757 1 Ack ID - U16
5976 0x1758 1 Status :
0 : Inactive
1 : Active
2 : Finished
3 : FinishedAndAck
- U8
5977 0x1759 1 Alarm Type
0 : None
1 : Unexpected Transfer
2 : Failed to Transfer
3 : Operating Factor Fault
4 : Max PWD Attempts
5 : Genset Failed to Start
6 : External Fault
- U8
5978 0x175A 1 Alarm cause :
0 : Cause Unknown
20 : Fault Active
- U8
5979 0x175B 1 Criticality :
0 : Information
1 : Warning
2 : Critical
- U8
5980 0x175C 2 Start date - DATETIME
5982 0x175E 2 Duration s U32

ALM Fault Current Status #3


Dec start address Hex start address Type Size Lock level Locked fcts Unlocked fcts
5998 0x176E Info 9 NONE READ READ

Dec address Hex address Words count Description Unit Data type
5998 0x176E 1 Ack ID - U16
5999 0x176F 1 Status :
0 : Inactive
1 : Active
2 : Finished
3 : FinishedAndAck
- U8
6000 0x1770 1 Alarm Type
0 : None
1 : Unexpected Transfer
2 : Failed to Transfer
3 : Operating Factor Fault
4 : Max PWD Attempts
5 : Genset Failed to Start
6 : External Fault
- U8
6001 0x1771 1 Alarm cause :
0 : Cause Unknown
20 : Fault Active
- U8
6002 0x1772 1 Criticality :
0 : Information
1 : Warning
2 : Critical
- U8
6003 0x1773 2 Start date - DATETIME
6005 0x1775 2 Duration s U32

ALM Fault Current Status #4


Dec start address Hex start address Type Size Lock level Locked fcts Unlocked fcts
6021 0x1785 Info 9 NONE READ READ

Dec address Hex address Words count Description Unit Data type
6021 0x1785 1 Ack ID - U16
6022 0x1786 1 Status :
0 : Inactive
1 : Active
2 : Finished
3 : FinishedAndAck
- U8
6023 0x1787 1 Alarm Type
0 : None
1 : Unexpected Transfer
2 : Failed to Transfer
3 : Operating Factor Fault
4 : Max PWD Attempts
5 : Genset Failed to Start
6 : External Fault
- U8
6024 0x1788 1 Alarm cause :
0 : Cause Unknown
20 : Fault Active
- U8
6025 0x1789 1 Criticality :
0 : Information
1 : Warning
2 : Critical
- U8
6026 0x178A 2 Start date - DATETIME
6028 0x178C 2 Duration s U32

ALM Fault Current Status #5


Dec start address Hex start address Type Size Lock level Locked fcts Unlocked fcts
6044 0x179C Info 9 NONE READ READ

Dec address Hex address Words count Description Unit Data type
6044 0x179C 1 Ack ID - U16
6045 0x179D 1 Status :
0 : Inactive
1 : Active
2 : Finished
3 : FinishedAndAck
- U8
6046 0x179E 1 Alarm Type
0 : None
1 : Unexpected Transfer
2 : Failed to Transfer
3 : Operating Factor Fault
4 : Max PWD Attempts
5 : Genset Failed to Start
6 : External Fault
- U8
6047 0x179F 1 Alarm cause :
0 : Cause Unknown
20 : Fault Active
- U8
6048 0x17A0 1 Criticality :
0 : Information
1 : Warning
2 : Critical
- U8
6049 0x17A1 2 Start date - DATETIME
6051 0x17A3 2 Duration s U32

ALM Fault Current Status #6


Dec start address Hex start address Type Size Lock level Locked fcts Unlocked fcts
6067 0x17B3 Info 9 NONE READ READ

Dec address Hex address Words count Description Unit Data type
6067 0x17B3 1 Ack ID - U16
6068 0x17B4 1 Status :
0 : Inactive
1 : Active
2 : Finished
3 : FinishedAndAck
- U8
6069 0x17B5 1 Alarm Type
0 : None
1 : Unexpected Transfer
2 : Failed to Transfer
3 : Operating Factor Fault
4 : Max PWD Attempts
5 : Genset Failed to Start
6 : External Fault
- U8
6070 0x17B6 1 Alarm cause :
0 : Cause Unknown
20 : Fault Active
- U8
6071 0x17B7 1 Criticality :
0 : Information
1 : Warning
2 : Critical
- U8
6072 0x17B8 2 Start date - DATETIME
6074 0x17BA 2 Duration s U32


Log


ALM Log


Command

Dec start address Hex start address Type Size Lock level Locked fcts Unlocked fcts
9120 0x23A0 Command 1 NONE WRITE_MANY WRITE_MANY

Dec address Hex address Words count Description Unit Data type
9120 0x23A0 1 Start record number (0 to 65534) or 65535 for last record - U16

Header

Dec start address Hex start address Type Size Lock level Locked fcts Unlocked fcts
9136 0x23B0 Header 3 NONE READ READ

Dec address Hex address Words count Description Unit Data type
9136 0x23B0 1 Next record number - U16
9137 0x23B1 1 Items count (max 7 per request) - U16
9138 0x23B2 1 Item size (words) - U16

Data

Dec start address Hex start address Type Size Lock level Locked fcts Unlocked fcts
9139 0x23B3 Data 21 NONE READ READ

Dec address Hex address Words count Description Unit Data type
9139 0x23B3 1 Alarm cause
0 : Cause Unknown
1 : Analog. High Th. Single
2 : Analog. High Th. Tri. And
3 : Analog. High Th. Tri. Or
4 : Analog. Low Th Single
5 : Analog. Low Th. Tri. And
6 : Analog. Low Th. Tri. Or
7 : Logical Active
8 : Combi. And
9 : Combi. Or
10 : EN50160 Active
11 : Inrush Active
12 : System Active
19 : Maintenance
20 : Fault
- U16_HEX
9140 0x23B4 1 Criticality :
0 : Information
1 : Warning
2 : Critical
- U8
9141 0x23B5 2 Start date - DATETIME
9143 0x23B7 2 Duration s U32
9145 0x23B9 2 Specific data 1 (depend on alarm type) - U32
9147 0x23BB 1 Specific data 2 (depend on alarm type) - U16
9148 0x23BC 1 Specific data 3 (depend on alarm type) - U16
9149 0x23BD 1 Specific data 4 (depend on alarm type) - U16
9150 0x23BE 1 Specific data 5 (depend on alarm type) - U16
9151 0x23BF 1 Specific data 6 (depend on alarm type) - U16
9152 0x23C0 4 Specific data 7 (depend on alarm type) - S64
9156 0x23C4 4 Specific data 8 (depend on alarm type) - S64





Settings


Hour/Date


Dec start address Hex start address Type Size Lock level Locked fcts Unlocked fcts
57600 0xE100 Date/Time command 6 NONE READ | WRITE | WRITE_MANY READ | WRITE | WRITE_MANY

Dec address Hex address Words count Description Unit Data type
57600 0xE100 1 Day - U8
57601 0xE101 1 Month - U8
57602 0xE102 1 Year - U8
57603 0xE103 1 Hour - U8
57604 0xE104 1 Minute - U8
57605 0xE105 1 Second - U8

Network and Load


Setup Network


Dec start address Hex start address Type Size Lock level Locked fcts Unlocked fcts
12288 0x3000 Settings 10 NONE READ | WRITE | WRITE_MANY READ | WRITE | WRITE_MANY

Dec address Hex address Words count Description Unit Data type
12288 0x3000 1 Network connection type
0 : Not defined
1 : 1P + N
2 : 2P
3 : 2P + N
4 : 3P
5 : 3P + N
7 : 3P + N / 1P + N
- U8
12289 0x3001 2 Nominal Voltage V U32
12291 0x3003 1 Nominal Frequency
0 : 50 Hz - eDefFnom_50Hz
1 : 60 Hz - eDefFnom_60Hz
- U8
12292 0x3004 1 Phase Rotation
0 : V1 - V2 - V3
1 : V1 - V3 - V2
- U8
12293 0x3005 1 Voltage transformer used
0 : NO
1 : YES
- U8
12294 0x3006 2 Voltage transformer rate : primary - U32
12296 0x3008 1 Voltage transformer rate : secondary - U16
12297 0x3009 1 Phase Rotation Check
0 : NO
1 : YES
- U8

Setup Threshold for up stream Voltages


Dec start address Hex start address Type Size Lock level Locked fcts Unlocked fcts
22272 0x5700 Settings 20 USER READ READ | WRITE | WRITE_MANY

Dec address Hex address Words count Description Unit Data type
22272 0x5700 1 Source 1 : Overvoltage threshold % U8
22273 0x5701 1 Source 1 : Overvoltage hysteresis threshold % U8
22274 0x5702 1 Source 1 : Undervoltage threshold % U8
22275 0x5703 1 Source 1 : Undervoltage hysteresis threshold % U8
22276 0x5704 1 Source 2 : Overvoltage threshold % U8
22277 0x5705 1 Source 2 : Overvoltage hysteresis threshold % U8
22278 0x5706 1 Source 2 : Undervoltage threshold % U8
22279 0x5707 1 Source 2 : Undervoltage hysteresis threshold % U8
22280 0x5708 1 Source 1 : Unbalanced voltage threshold % U8
22281 0x5709 1 Source 1 : Unbalanced voltage hysteresis threshold % U8
22282 0x570A 1 Source 2 : Unbalanced voltage threshold % U8
22283 0x570B 1 Source 2 : Unbalanced voltage hysteresis threshold % U8
22284 0x570C 1 Source 1 : Overfrequency threshold % / 10 U16
22285 0x570D 1 Source 1 : Overfrequency hysteresis threshold % / 10 U16
22286 0x570E 1 Source 1 : Underfrequency threshold % / 10 U16
22287 0x570F 1 Source 1 : Underfrequency hysteresis threshold % / 10 U16
22288 0x5710 1 Source 2 : Overfrequency threshold % / 10 U16
22289 0x5711 1 Source 2 : Overfrequency hysteresis threshold % / 10 U16
22290 0x5712 1 Source 2 : Underfrequency threshold % / 10 U16
22291 0x5713 1 Source 2 : Underfrequency hysteresis threshold % / 10 U16


Automation


ATS Aplication


Dec start address Hex start address Type Size Lock level Locked fcts Unlocked fcts
22064 0x5630 Settings 53 USER READ READ | WRITE | WRITE_MANY

Dec address Hex address Words count Description Unit Data type
22064 0x5630 1 Type of Application
0 : M-M
1 : M-G
2 : G-G
- U8
22065 0x5631 1 Reserved - -
22066 0x5632 1 External position command logic type
0 : CONTACT
1 : IMPULSE
- U8
22067 0x5633 1 Priority - Power Supply
0 : Network
1 : Source 1
2 : Source 2
- U8
22068 0x5634 1 Priority - Test On Load
0 : NO
1 : YES
- U8
22069 0x5635 1 Priority - External Order On Load
0 : NO
1 : YES
- U8
22070 0x5636 1 Manual retransfer
0 : NO
1 : YES
- U8
22071 0x5637 1 Reserved - -
22072 0x5638 1 Reserved - -
22073 0x5639 1 Reserved - -
22074 0x563A 1 Switch Technology
1 : ATyS r/d
2 : Contactor
3 : Circuit Breaker
4 : ATyS DT
- U8
22075 0x563B 1 Test Button use
0 : Test Off Load
1 : Test On Load
- U8
22076 0x563C 1 Op. Factor : Nb of operations - U8
22077 0x563D 1 Op. Factor : Time for nb of operations min U8
22078 0x563E 16 Source1 Name - STRING_NORM
22094 0x564E 16 Source2 Name - STRING_NORM
22110 0x565E 1 Reserved - -
22111 0x565F 1 Retry number - U8
22112 0x5660 1 Retry delay s 10⁻³ U16
22113 0x5661 1 Reserved - -
22114 0x5662 1 Reserved - -
22115 0x5663 1 Power Up In Auto
0 : NO
1 : YES
- U8
22116 0x5664 1 Reserved - -

Timers


Dec start address Hex start address Type Size Lock level Locked fcts Unlocked fcts
22016 0x5600 Settings 36 USER READ READ | WRITE | WRITE_MANY

Dec address Hex address Words count Description Unit Data type
22016 0x5600 1 1FT Source1 Failure Timer s 10⁻¹ U16
22017 0x5601 1 1RT Source1 Available/Return Timer s U16
22018 0x5602 1 1CT Source1 Genset Cooldown timer s U16
22019 0x5603 1 Reserved - -
22020 0x5604 1 1ST Source1 Start TimeOut timer s U16
22021 0x5605 1 Reserved - -
22022 0x5606 1 Reserved - -
22023 0x5607 1 2FT Source2 Failure Timer s 10⁻¹ U16
22024 0x5608 1 2RT Source2 Available/Return Timer s U16
22025 0x5609 1 2CT Source2 Genset Cooldown timer s U16
22026 0x560A 1 Reserved - -
22027 0x560B 1 2ST Source2 Start TimeOut timer s U16
22028 0x560C 1 Reserved - -
22029 0x560D 1 Reserved - -
22030 0x560E 1 DBT Dead Band timer s U16
22031 0x560F 1 Limit_TOT Test on load is limited
0 : unlimited
1 : limited
- U8
22032 0x5610 1 TOT Test on load duration timer s U16
22033 0x5611 1 T3T Test on load end timer s U16
22034 0x5612 1 Limit_TFT Test off load is limited
0 : unlimited
1 : limited
- U8
22035 0x5613 1 TFT Test off load duration timer s U16
22036 0x5614 1 E1T Time before external order on load s U16
22037 0x5615 1 E3T Time after external order on load s U16
22038 0x5616 1 Limit_E2T External order on load is limited
0 : unlimited
1 : limited
- U8
22039 0x5617 1 E2T External order on load duration s U16
22040 0x5618 1 E5T Time before external order off load s U16
22041 0x5619 1 E7T Time after external order off load s U16
22042 0x561A 1 Limit_E6T External order off load is limited
0 : unlimited
1 : limited
- U8
22043 0x561B 1 E6T External order off load duration s U16
22044 0x561C 1 Reserved - -
22045 0x561D 1 Reserved - -
22046 0x561E 1 Reserved - -
22047 0x561F 1 DRT: Dynamic return timer s U16
22048 0x5620 1 Reserved - -
22049 0x5621 1 Reserved - -
22050 0x5622 1 Reserved - -
22051 0x5623 1 Reserved - -

Exerciser


Dec start address Hex start address Type Size Lock level Locked fcts Unlocked fcts
24064 0x5E00 Settings 9 USER READ READ | WRITE | WRITE_MANY

Dec address Hex address Words count Description Unit Data type
24064 0x5E00 1 Custom1: Exerciser Type set
0 : Not Used
1 : For TON
2 : For TOF
- U8
24065 0x5E01 1 Reserved - -
24066 0x5E02 1 Custom1: Periodic Schedule Set
0 : Daily
1 : Weekly
2 : Bi Weekly
3 : Monthly
4 : Yearly
5 : Non Cyclic
6 : Bi Daily
7 : Bi Monthly
8 : Hexa Monthly
9 : 28 Days
- U8
24067 0x5E03 2 Custom1 Start Time - DATETIME
24069 0x5E05 1 Custom1 Duration s U16
24070 0x5E06 2 Custom1 End Time - DATETIME
24072 0x5E08 1 Min Idle Time to Run min U16


Inputs and outputs


Output Relay


Dec start address Hex start address Type Size Lock level Locked fcts Unlocked fcts
16384 0x4000 Settings 13 USER READ READ | WRITE | WRITE_MANY

Dec address Hex address Words count Description Unit Data type
16384 0x4000 1 Output 1 function
0 : --- - None
70 : PO1 - Switch to pos 1
71 : PO2 - Switch to pos 2
72 : PO0 - Switch to pos 0
73 : PA0 - Switch A to pos 0 (S1)
74 : PB0 - Switch B to pos 0 (S2)
77 : S1A - Source 1 available
78 : S2A - Source 2 available
79 : SCA - At Least 1 source avail
80 : S1U - Source 1 unavailable
81 : S2U - Source 2 unavailable
82 : AC1 - Source 1 closed
83 : AC2 - Source 2 closed
84 : AC0 - Off Position
88 : FLT - Faults active
94 : ROS - TON or EON in progress
109 : AUD - Critical Alarm Active
- U8
16385 0x4001 1 Output 2 function
0 : --- - None
70 : PO1 - Switch to pos 1
71 : PO2 - Switch to pos 2
72 : PO0 - Switch to pos 0
73 : PA0 - Switch A to pos 0 (S1)
74 : PB0 - Switch B to pos 0 (S2)
77 : S1A - Source 1 available
78 : S2A - Source 2 available
79 : SCA - At Least 1 source avail
80 : S1U - Source 1 unavailable
81 : S2U - Source 2 unavailable
82 : AC1 - Source 1 closed
83 : AC2 - Source 2 closed
84 : AC0 - Off Position
88 : FLT - Faults active
94 : ROS - TON or EON in progress
109 : AUD - Critical Alarm Active
- U8
16386 0x4002 1 Output 3 function
0 : --- - None
70 : PO1 - Switch to pos 1
71 : PO2 - Switch to pos 2
72 : PO0 - Switch to pos 0
73 : PA0 - Switch A to pos 0 (S1)
74 : PB0 - Switch B to pos 0 (S2)
77 : S1A - Source 1 available
78 : S2A - Source 2 available
79 : SCA - At Least 1 source avail
80 : S1U - Source 1 unavailable
81 : S2U - Source 2 unavailable
82 : AC1 - Source 1 closed
83 : AC2 - Source 2 closed
84 : AC0 - Off Position
88 : FLT - Faults active
94 : ROS - TON or EON in progress
109 : AUD - Critical Alarm Active
- U8
16387 0x4003 1 Output 4 function
0 : --- - None
70 : PO1 - Switch to pos 1
71 : PO2 - Switch to pos 2
72 : PO0 - Switch to pos 0
73 : PA0 - Switch A to pos 0 (S1)
74 : PB0 - Switch B to pos 0 (S2)
77 : S1A - Source 1 available
78 : S2A - Source 2 available
79 : SCA - At Least 1 source avail
80 : S1U - Source 1 unavailable
81 : S2U - Source 2 unavailable
82 : AC1 - Source 1 closed
83 : AC2 - Source 2 closed
84 : AC0 - Off Position
88 : FLT - Faults active
94 : ROS - TON or EON in progress
109 : AUD - Critical Alarm Active
- U8
16388 0x4004 1 Output 1 type
0 : NO
1 : NC
- U8
16389 0x4005 1 Output 2 type
0 : NO
1 : NC
- U8
16390 0x4006 1 Output 3 type
0 : NO
1 : NC
- U8
16391 0x4007 1 Output 4 type
0 : NO
1 : NC
- U8
16392 0x4008 1 Pulse length (RTSE control in pulse mode) s 10⁻³ U16
16393 0x4009 1 Output 5 function (Genset S1)
0 : --- - None
75 : GS1 - Genset Source 1 start
77 : S1A - Source 1 available
78 : S2A - Source 2 available
79 : SCA - At Least 1 source avail
80 : S1U - Source 1 unavailable
81 : S2U - Source 2 unavailable
82 : AC1 - Source 1 closed
83 : AC2 - Source 2 closed
84 : AC0 - Off Position
88 : FLT - Faults active
94 : ROS - TON or EON in progress
109 : AUD - Critical Alarm Active
- U8
16394 0x400A 1 Output 6 function (Genset S2)
0 : --- - None
75 : GS1 - Genset Source 1 start
76 : GS2 - Genset Source 2 start
77 : S1A - Source 1 available
78 : S2A - Source 2 available
79 : SCA - At Least 1 source avail
80 : S1U - Source 1 unavailable
81 : S2U - Source 2 unavailable
82 : AC1 - Source 1 closed
83 : AC2 - Source 2 closed
84 : AC0 - Off Position
88 : FLT - Faults active
94 : ROS - TON or EON in progress
109 : AUD - Critical Alarm Active
- U8
16395 0x400B 1 Output 5 type
0 : NO
1 : NC
- U8
16396 0x400C 1 Output 6 type
0 : NO
1 : NC
- U8

Input


Dec start address Hex start address Type Size Lock level Locked fcts Unlocked fcts
11296 0x2C20 Settings 12 USER READ READ | WRITE | WRITE_MANY

Dec address Hex address Words count Description Unit Data type
11296 0x2C20 1 Input 1 function
0 : --- - None
21 : INH - Inhibition
22 : INHP - Partial Inhibition
23 : INHT - Total Inhibition
24 : TON - Test on load
25 : TOF - Test off load
26 : EON - External order on load
27 : EOF - External order off load
28 : MRT - Manual Retransfer
29 : PRI - Change Priority
30 : SS1 - Validation Stabilization source 1
31 : SS2 - Validation Stabilization source 2
32 : ALE - External Alarm
33 : FTE - External Fault
36 : MSR - Priority test on load
37 : OA1 - Override source 1 available
38 : OA2 - Override source 2 available
39 : OU1 - Override source 1 unavailable
40 : OU2 - Override source 2 unavailable
41 : RST - Reset faults state
43 : AC1 - Switch position 1
44 : AC2 - Switch position 2
45 : AC0 - Switch position 0
46 : AC0A - Switch A position 0
47 : AC0B - Switch B position 0
48 : MAN - RTSE in manual mode
49 : LCK - RTSE locked
50 : CHP - Change Position
53 : PS1 - Go to position 1
54 : PS2 - Go to position 2
55 : PS0 - Go to position 0
57 : BLK - Interlocking blocked
58 : TP1 - Trip S1
59 : TP2 - Trip S2
61 : EST - Emergency Stop
64 : BCT - Bypass Current Timer
- U8
11297 0x2C21 1 Input 2 function
0 : --- - None
21 : INH - Inhibition
22 : INHP - Partial Inhibition
23 : INHT - Total Inhibition
24 : TON - Test on load
25 : TOF - Test off load
26 : EON - External order on load
27 : EOF - External order off load
28 : MRT - Manual Retransfer
29 : PRI - Change Priority
30 : SS1 - Validation Stabilization source 1
31 : SS2 - Validation Stabilization source 2
32 : ALE - External Alarm
33 : FTE - External Fault
36 : MSR - Priority test on load
37 : OA1 - Override source 1 available
38 : OA2 - Override source 2 available
39 : OU1 - Override source 1 unavailable
40 : OU2 - Override source 2 unavailable
41 : RST - Reset faults state
43 : AC1 - Switch position 1
44 : AC2 - Switch position 2
45 : AC0 - Switch position 0
46 : AC0A - Switch A position 0
47 : AC0B - Switch B position 0
48 : MAN - RTSE in manual mode
49 : LCK - RTSE locked
50 : CHP - Change Position
53 : PS1 - Go to position 1
54 : PS2 - Go to position 2
55 : PS0 - Go to position 0
57 : BLK - Interlocking blocked
58 : TP1 - Trip S1
59 : TP2 - Trip S2
61 : EST - Emergency Stop
64 : BCT - Bypass Current Timer
- U8
11298 0x2C22 1 Input 3 function
0 : --- - None
21 : INH - Inhibition
22 : INHP - Partial Inhibition
23 : INHT - Total Inhibition
24 : TON - Test on load
25 : TOF - Test off load
26 : EON - External order on load
27 : EOF - External order off load
28 : MRT - Manual Retransfer
29 : PRI - Change Priority
30 : SS1 - Validation Stabilization source 1
31 : SS2 - Validation Stabilization source 2
32 : ALE - External Alarm
33 : FTE - External Fault
36 : MSR - Priority test on load
37 : OA1 - Override source 1 available
38 : OA2 - Override source 2 available
39 : OU1 - Override source 1 unavailable
40 : OU2 - Override source 2 unavailable
41 : RST - Reset faults state
43 : AC1 - Switch position 1
44 : AC2 - Switch position 2
45 : AC0 - Switch position 0
46 : AC0A - Switch A position 0
47 : AC0B - Switch B position 0
48 : MAN - RTSE in manual mode
49 : LCK - RTSE locked
50 : CHP - Change Position
53 : PS1 - Go to position 1
54 : PS2 - Go to position 2
55 : PS0 - Go to position 0
57 : BLK - Interlocking blocked
58 : TP1 - Trip S1
59 : TP2 - Trip S2
61 : EST - Emergency Stop
64 : BCT - Bypass Current Timer
- U8
11299 0x2C23 1 Input 4 function
0 : --- - None
21 : INH - Inhibition
22 : INHP - Partial Inhibition
23 : INHT - Total Inhibition
24 : TON - Test on load
25 : TOF - Test off load
26 : EON - External order on load
27 : EOF - External order off load
28 : MRT - Manual Retransfer
29 : PRI - Change Priority
30 : SS1 - Validation Stabilization source 1
31 : SS2 - Validation Stabilization source 2
32 : ALE - External Alarm
33 : FTE - External Fault
36 : MSR - Priority test on load
37 : OA1 - Override source 1 available
38 : OA2 - Override source 2 available
39 : OU1 - Override source 1 unavailable
40 : OU2 - Override source 2 unavailable
41 : RST - Reset faults state
43 : AC1 - Switch position 1
44 : AC2 - Switch position 2
45 : AC0 - Switch position 0
46 : AC0A - Switch A position 0
47 : AC0B - Switch B position 0
48 : MAN - RTSE in manual mode
49 : LCK - RTSE locked
50 : CHP - Change Position
53 : PS1 - Go to position 1
54 : PS2 - Go to position 2
55 : PS0 - Go to position 0
57 : BLK - Interlocking blocked
58 : TP1 - Trip S1
59 : TP2 - Trip S2
61 : EST - Emergency Stop
64 : BCT - Bypass Current Timer
- U8
11300 0x2C24 1 Input 5 function
0 : --- - None
21 : INH - Inhibition
22 : INHP - Partial Inhibition
23 : INHT - Total Inhibition
24 : TON - Test on load
25 : TOF - Test off load
26 : EON - External order on load
27 : EOF - External order off load
28 : MRT - Manual Retransfer
29 : PRI - Change Priority
30 : SS1 - Validation Stabilization source 1
31 : SS2 - Validation Stabilization source 2
32 : ALE - External Alarm
33 : FTE - External Fault
36 : MSR - Priority test on load
37 : OA1 - Override source 1 available
38 : OA2 - Override source 2 available
39 : OU1 - Override source 1 unavailable
40 : OU2 - Override source 2 unavailable
41 : RST - Reset faults state
43 : AC1 - Switch position 1
44 : AC2 - Switch position 2
45 : AC0 - Switch position 0
46 : AC0A - Switch A position 0
47 : AC0B - Switch B position 0
48 : MAN - RTSE in manual mode
49 : LCK - RTSE locked
50 : CHP - Change Position
53 : PS1 - Go to position 1
54 : PS2 - Go to position 2
55 : PS0 - Go to position 0
57 : BLK - Interlocking blocked
58 : TP1 - Trip S1
59 : TP2 - Trip S2
61 : EST - Emergency Stop
64 : BCT - Bypass Current Timer
- U8
11301 0x2C25 1 Input 6 function
0 : --- - None
21 : INH - Inhibition
22 : INHP - Partial Inhibition
23 : INHT - Total Inhibition
24 : TON - Test on load
25 : TOF - Test off load
26 : EON - External order on load
27 : EOF - External order off load
28 : MRT - Manual Retransfer
29 : PRI - Change Priority
30 : SS1 - Validation Stabilization source 1
31 : SS2 - Validation Stabilization source 2
32 : ALE - External Alarm
33 : FTE - External Fault
36 : MSR - Priority test on load
37 : OA1 - Override source 1 available
38 : OA2 - Override source 2 available
39 : OU1 - Override source 1 unavailable
40 : OU2 - Override source 2 unavailable
41 : RST - Reset faults state
43 : AC1 - Switch position 1
44 : AC2 - Switch position 2
45 : AC0 - Switch position 0
46 : AC0A - Switch A position 0
47 : AC0B - Switch B position 0
48 : MAN - RTSE in manual mode
49 : LCK - RTSE locked
50 : CHP - Change Position
53 : PS1 - Go to position 1
54 : PS2 - Go to position 2
55 : PS0 - Go to position 0
57 : BLK - Interlocking blocked
58 : TP1 - Trip S1
59 : TP2 - Trip S2
61 : EST - Emergency Stop
64 : BCT - Bypass Current Timer
- U8
11302 0x2C26 1 Input 1 type
0 : NO
1 : NC
- U8
11303 0x2C27 1 Input 2 type
0 : NO
1 : NC
- U8
11304 0x2C28 1 Input 3 type
0 : NO
1 : NC
- U8
11305 0x2C29 1 Input 4 type
0 : NO
1 : NC
- U8
11306 0x2C2A 1 Input 5 type
0 : NO
1 : NC
- U8
11307 0x2C2B 1 Input 6 type
0 : NO
1 : NC
- U8


Communication


Slave address


Dec start address Hex start address Type Size Lock level Locked fcts Unlocked fcts
57344 0xE000 Settings 1 USER READ READ | WRITE | WRITE_MANY

Dec address Hex address Words count Description Unit Data type
57344 0xE000 1 Slave Address - U8

Modbus slave connection settings RS485


Dec start address Hex start address Type Size Lock level Locked fcts Unlocked fcts
57345 0xE001 Settings 3 USER READ READ | WRITE | WRITE_MANY

Dec address Hex address Words count Description Unit Data type
57345 0xE001 1 Baudrate :
0 : 1200
1 : 2400
2 : 4800
3 : 9600
4 : 19200
5 : 38400
6 : 57600
7 : 115200
- U8
57346 0xE002 1 Stop bit :
0 : 1
1 : 2
- U8
57347 0xE003 1 Parity :
0 : None
1 : Odd
2 : Even
- U8


Display


Screen interface settings


Dec start address Hex start address Type Size Lock level Locked fcts Unlocked fcts
28928 0x7100 Settings 7 USER READ READ | WRITE | WRITE_MANY

Dec address Hex address Words count Description Unit Data type
28928 0x7100 1 Language
0 : English
1 : French
2 : German
3 : Italian
4 : Polish
5 : Spanish
6 : Turkish
8 : Chinese
9 : Portuguese
- U16
28929 0x7101 1 Backlight intensity - U16
28930 0x7102 1 Backlight timeout s U16
28931 0x7103 1 Contrast
0 : Dark
1 : Medium
2 : Light
- U16
28932 0x7104 1 Reserved - -
28933 0x7105 1 Reserved - -
28934 0x7106 1 LampTest Duration s U16


Alarms


Analog-Maintenance


ALM Ana Maint Settings #1


Dec start address Hex start address Type Size Lock level Locked fcts Unlocked fcts
4368 0x1110 Settings 33 USER READ READ | WRITE | WRITE_MANY

Dec address Hex address Words count Description Unit Data type
4368 0x1110 1 Status :
0 : Disabled
1 : Enabled
- U8
4369 0x1111 1 Criticality :
0 : Information
1 : Warning
2 : Critical
- U8
4370 0x1112 1 Input for ack
0 : Input 1
1 : Input 2
2 : Input 3
3 : Input 4
4 : Input 5
5 : Input 6
255 : Not used
- U8
4371 0x1113 1 Acknowledgement method :
0 : None
1 : MODBUS only
2 : Logical input
- U8
4372 0x1114 1 Output for report
0 : Output 1
1 : Output 2
2 : Output 3
3 : Output 4
4 : Output 5
5 : Output 6
255 : Not used
- U8
4373 0x1115 2 Analog variable (ServiceID)
5206 : Total Cycle Counter
5415 : Total Switch Counter
5434 : Genset S1 Activation Time
5435 : Genset S2 Activation Time
5436 : Genset S1 On Load Time
5437 : Genset S2 On Load Time
156094 : Time Since Last Inspection
- U32
4375 0x1117 1 Analog variable (Instance index) - U16
4376 0x1118 1 Reserved - -
4377 0x1119 1 Variable data access :
0 : Single
1 : Triple (logical AND)
2 : Triple (logical OR)
3 : Maintenance
- U8
4378 0x111A 2 High threshold - S32
4380 0x111C 2 Low threshold - S32
4382 0x111E 1 Hysteresis % / 10 U16
4383 0x111F 1 Startup delay s / 2 U16
4384 0x1120 1 Dropout delay s / 2 U16
4385 0x1121 16 Name - STRING_NORM

ALM Ana Maint Settings #2


Dec start address Hex start address Type Size Lock level Locked fcts Unlocked fcts
4401 0x1131 Settings 33 USER READ READ | WRITE | WRITE_MANY

Dec address Hex address Words count Description Unit Data type
4401 0x1131 1 Status :
0 : Disabled
1 : Enabled
- U8
4402 0x1132 1 Criticality :
0 : Information
1 : Warning
2 : Critical
- U8
4403 0x1133 1 Input for ack
0 : Input 1
1 : Input 2
2 : Input 3
3 : Input 4
4 : Input 5
5 : Input 6
255 : Not used
- U8
4404 0x1134 1 Acknowledgement method :
0 : None
1 : MODBUS only
2 : Logical input
- U8
4405 0x1135 1 Output for report
0 : Output 1
1 : Output 2
2 : Output 3
3 : Output 4
4 : Output 5
5 : Output 6
255 : Not used
- U8
4406 0x1136 2 Analog variable (ServiceID)
5206 : Total Cycle Counter
5415 : Total Switch Counter
5434 : Genset S1 Activation Time
5435 : Genset S2 Activation Time
5436 : Genset S1 On Load Time
5437 : Genset S2 On Load Time
156094 : Time Since Last Inspection
- U32
4408 0x1138 1 Analog variable (Instance index) - U16
4409 0x1139 1 Reserved - -
4410 0x113A 1 Variable data access :
0 : Single
1 : Triple (logical AND)
2 : Triple (logical OR)
3 : Maintenance
- U8
4411 0x113B 2 High threshold - S32
4413 0x113D 2 Low threshold - S32
4415 0x113F 1 Hysteresis % / 10 U16
4416 0x1140 1 Startup delay s / 2 U16
4417 0x1141 1 Dropout delay s / 2 U16
4418 0x1142 16 Name - STRING_NORM

ALM Ana Maint Settings #3


Dec start address Hex start address Type Size Lock level Locked fcts Unlocked fcts
4434 0x1152 Settings 33 USER READ READ | WRITE | WRITE_MANY

Dec address Hex address Words count Description Unit Data type
4434 0x1152 1 Status :
0 : Disabled
1 : Enabled
- U8
4435 0x1153 1 Criticality :
0 : Information
1 : Warning
2 : Critical
- U8
4436 0x1154 1 Input for ack
0 : Input 1
1 : Input 2
2 : Input 3
3 : Input 4
4 : Input 5
5 : Input 6
255 : Not used
- U8
4437 0x1155 1 Acknowledgement method :
0 : None
1 : MODBUS only
2 : Logical input
- U8
4438 0x1156 1 Output for report
0 : Output 1
1 : Output 2
2 : Output 3
3 : Output 4
4 : Output 5
5 : Output 6
255 : Not used
- U8
4439 0x1157 2 Analog variable (ServiceID)
5206 : Total Cycle Counter
5415 : Total Switch Counter
5434 : Genset S1 Activation Time
5435 : Genset S2 Activation Time
5436 : Genset S1 On Load Time
5437 : Genset S2 On Load Time
156094 : Time Since Last Inspection
- U32
4441 0x1159 1 Analog variable (Instance index) - U16
4442 0x115A 1 Reserved - -
4443 0x115B 1 Variable data access :
0 : Single
1 : Triple (logical AND)
2 : Triple (logical OR)
3 : Maintenance
- U8
4444 0x115C 2 High threshold - S32
4446 0x115E 2 Low threshold - S32
4448 0x1160 1 Hysteresis % / 10 U16
4449 0x1161 1 Startup delay s / 2 U16
4450 0x1162 1 Dropout delay s / 2 U16
4451 0x1163 16 Name - STRING_NORM

ALM Ana Maint Settings #4


Dec start address Hex start address Type Size Lock level Locked fcts Unlocked fcts
4467 0x1173 Settings 33 USER READ READ | WRITE | WRITE_MANY

Dec address Hex address Words count Description Unit Data type
4467 0x1173 1 Status :
0 : Disabled
1 : Enabled
- U8
4468 0x1174 1 Criticality :
0 : Information
1 : Warning
2 : Critical
- U8
4469 0x1175 1 Input for ack
0 : Input 1
1 : Input 2
2 : Input 3
3 : Input 4
4 : Input 5
5 : Input 6
255 : Not used
- U8
4470 0x1176 1 Acknowledgement method :
0 : None
1 : MODBUS only
2 : Logical input
- U8
4471 0x1177 1 Output for report
0 : Output 1
1 : Output 2
2 : Output 3
3 : Output 4
4 : Output 5
5 : Output 6
255 : Not used
- U8
4472 0x1178 2 Analog variable (ServiceID)
5206 : Total Cycle Counter
5415 : Total Switch Counter
5434 : Genset S1 Activation Time
5435 : Genset S2 Activation Time
5436 : Genset S1 On Load Time
5437 : Genset S2 On Load Time
156094 : Time Since Last Inspection
- U32
4474 0x117A 1 Analog variable (Instance index) - U16
4475 0x117B 1 Reserved - -
4476 0x117C 1 Variable data access :
0 : Single
1 : Triple (logical AND)
2 : Triple (logical OR)
3 : Maintenance
- U8
4477 0x117D 2 High threshold - S32
4479 0x117F 2 Low threshold - S32
4481 0x1181 1 Hysteresis % / 10 U16
4482 0x1182 1 Startup delay s / 2 U16
4483 0x1183 1 Dropout delay s / 2 U16
4484 0x1184 16 Name - STRING_NORM

ALM Ana Maint Settings #5


Dec start address Hex start address Type Size Lock level Locked fcts Unlocked fcts
4500 0x1194 Settings 33 USER READ READ | WRITE | WRITE_MANY

Dec address Hex address Words count Description Unit Data type
4500 0x1194 1 Status :
0 : Disabled
1 : Enabled
- U8
4501 0x1195 1 Criticality :
0 : Information
1 : Warning
2 : Critical
- U8
4502 0x1196 1 Input for ack
0 : Input 1
1 : Input 2
2 : Input 3
3 : Input 4
4 : Input 5
5 : Input 6
255 : Not used
- U8
4503 0x1197 1 Acknowledgement method :
0 : None
1 : MODBUS only
2 : Logical input
- U8
4504 0x1198 1 Output for report
0 : Output 1
1 : Output 2
2 : Output 3
3 : Output 4
4 : Output 5
5 : Output 6
255 : Not used
- U8
4505 0x1199 2 Analog variable (ServiceID)
5206 : Total Cycle Counter
5415 : Total Switch Counter
5434 : Genset S1 Activation Time
5435 : Genset S2 Activation Time
5436 : Genset S1 On Load Time
5437 : Genset S2 On Load Time
156094 : Time Since Last Inspection
- U32
4507 0x119B 1 Analog variable (Instance index) - U16
4508 0x119C 1 Reserved - -
4509 0x119D 1 Variable data access :
0 : Single
1 : Triple (logical AND)
2 : Triple (logical OR)
3 : Maintenance
- U8
4510 0x119E 2 High threshold - S32
4512 0x11A0 2 Low threshold - S32
4514 0x11A2 1 Hysteresis % / 10 U16
4515 0x11A3 1 Startup delay s / 2 U16
4516 0x11A4 1 Dropout delay s / 2 U16
4517 0x11A5 16 Name - STRING_NORM

ALM Ana Maint Settings #6


Dec start address Hex start address Type Size Lock level Locked fcts Unlocked fcts
4533 0x11B5 Settings 33 USER READ READ | WRITE | WRITE_MANY

Dec address Hex address Words count Description Unit Data type
4533 0x11B5 1 Status :
0 : Disabled
1 : Enabled
- U8
4534 0x11B6 1 Criticality :
0 : Information
1 : Warning
2 : Critical
- U8
4535 0x11B7 1 Input for ack
0 : Input 1
1 : Input 2
2 : Input 3
3 : Input 4
4 : Input 5
5 : Input 6
255 : Not used
- U8
4536 0x11B8 1 Acknowledgement method :
0 : None
1 : MODBUS only
2 : Logical input
- U8
4537 0x11B9 1 Output for report
0 : Output 1
1 : Output 2
2 : Output 3
3 : Output 4
4 : Output 5
5 : Output 6
255 : Not used
- U8
4538 0x11BA 2 Analog variable (ServiceID)
5206 : Total Cycle Counter
5415 : Total Switch Counter
5434 : Genset S1 Activation Time
5435 : Genset S2 Activation Time
5436 : Genset S1 On Load Time
5437 : Genset S2 On Load Time
156094 : Time Since Last Inspection
- U32
4540 0x11BC 1 Analog variable (Instance index) - U16
4541 0x11BD 1 Reserved - -
4542 0x11BE 1 Variable data access :
0 : Single
1 : Triple (logical AND)
2 : Triple (logical OR)
3 : Maintenance
- U8
4543 0x11BF 2 High threshold - S32
4545 0x11C1 2 Low threshold - S32
4547 0x11C3 1 Hysteresis % / 10 U16
4548 0x11C4 1 Startup delay s / 2 U16
4549 0x11C5 1 Dropout delay s / 2 U16
4550 0x11C6 16 Name - STRING_NORM


Logical


ALM Log Settings #1


Dec start address Hex start address Type Size Lock level Locked fcts Unlocked fcts
5632 0x1600 Settings 24 USER READ READ | WRITE | WRITE_MANY

Dec address Hex address Words count Description Unit Data type
5632 0x1600 1 Status :
0 : Disabled
1 : Enabled
- U8
5633 0x1601 1 Criticality :
0 : Information
1 : Warning
2 : Critical
- U8
5634 0x1602 1 Acknowledgement method :
0 : None
1 : MODBUS only
2 : Logical input
- U8
5635 0x1603 1 Input for ack
0 : Input 1
1 : Input 2
2 : Input 3
3 : Input 4
4 : Input 5
5 : Input 6
255 : Not used
- U8
5636 0x1604 1 Output for report
0 : Output 1
1 : Output 2
2 : Output 3
3 : Output 4
4 : Output 5
5 : Output 6
255 : Not used
- U8
5637 0x1605 1 Logical input
0 : Input 1
1 : Input 2
2 : Input 3
3 : Input 4
4 : Input 5
5 : Input 6
255 : Not used
- U8
5638 0x1606 1 Startup delay s / 2 U16
5639 0x1607 1 Dropout delay s / 2 U16
5640 0x1608 16 Name - STRING_NORM

ALM Log Settings #2


Dec start address Hex start address Type Size Lock level Locked fcts Unlocked fcts
5656 0x1618 Settings 24 USER READ READ | WRITE | WRITE_MANY

Dec address Hex address Words count Description Unit Data type
5656 0x1618 1 Status :
0 : Disabled
1 : Enabled
- U8
5657 0x1619 1 Criticality :
0 : Information
1 : Warning
2 : Critical
- U8
5658 0x161A 1 Acknowledgement method :
0 : None
1 : MODBUS only
2 : Logical input
- U8
5659 0x161B 1 Input for ack
0 : Input 1
1 : Input 2
2 : Input 3
3 : Input 4
4 : Input 5
5 : Input 6
255 : Not used
- U8
5660 0x161C 1 Output for report
0 : Output 1
1 : Output 2
2 : Output 3
3 : Output 4
4 : Output 5
5 : Output 6
255 : Not used
- U8
5661 0x161D 1 Logical input
0 : Input 1
1 : Input 2
2 : Input 3
3 : Input 4
4 : Input 5
5 : Input 6
255 : Not used
- U8
5662 0x161E 1 Startup delay s / 2 U16
5663 0x161F 1 Dropout delay s / 2 U16
5664 0x1620 16 Name - STRING_NORM

ALM Log Settings #3


Dec start address Hex start address Type Size Lock level Locked fcts Unlocked fcts
5680 0x1630 Settings 24 USER READ READ | WRITE | WRITE_MANY

Dec address Hex address Words count Description Unit Data type
5680 0x1630 1 Status :
0 : Disabled
1 : Enabled
- U8
5681 0x1631 1 Criticality :
0 : Information
1 : Warning
2 : Critical
- U8
5682 0x1632 1 Acknowledgement method :
0 : None
1 : MODBUS only
2 : Logical input
- U8
5683 0x1633 1 Input for ack
0 : Input 1
1 : Input 2
2 : Input 3
3 : Input 4
4 : Input 5
5 : Input 6
255 : Not used
- U8
5684 0x1634 1 Output for report
0 : Output 1
1 : Output 2
2 : Output 3
3 : Output 4
4 : Output 5
5 : Output 6
255 : Not used
- U8
5685 0x1635 1 Logical input
0 : Input 1
1 : Input 2
2 : Input 3
3 : Input 4
4 : Input 5
5 : Input 6
255 : Not used
- U8
5686 0x1636 1 Startup delay s / 2 U16
5687 0x1637 1 Dropout delay s / 2 U16
5688 0x1638 16 Name - STRING_NORM

ALM Log Settings #4


Dec start address Hex start address Type Size Lock level Locked fcts Unlocked fcts
5704 0x1648 Settings 24 USER READ READ | WRITE | WRITE_MANY

Dec address Hex address Words count Description Unit Data type
5704 0x1648 1 Status :
0 : Disabled
1 : Enabled
- U8
5705 0x1649 1 Criticality :
0 : Information
1 : Warning
2 : Critical
- U8
5706 0x164A 1 Acknowledgement method :
0 : None
1 : MODBUS only
2 : Logical input
- U8
5707 0x164B 1 Input for ack
0 : Input 1
1 : Input 2
2 : Input 3
3 : Input 4
4 : Input 5
5 : Input 6
255 : Not used
- U8
5708 0x164C 1 Output for report
0 : Output 1
1 : Output 2
2 : Output 3
3 : Output 4
4 : Output 5
5 : Output 6
255 : Not used
- U8
5709 0x164D 1 Logical input
0 : Input 1
1 : Input 2
2 : Input 3
3 : Input 4
4 : Input 5
5 : Input 6
255 : Not used
- U8
5710 0x164E 1 Startup delay s / 2 U16
5711 0x164F 1 Dropout delay s / 2 U16
5712 0x1650 16 Name - STRING_NORM


System


ALM Sys Settings #1


Dec start address Hex start address Type Size Lock level Locked fcts Unlocked fcts
6656 0x1A00 Settings 8 USER READ READ | WRITE | WRITE_MANY

Dec address Hex address Words count Description Unit Data type
6656 0x1A00 1 Status :
0 : Disabled
1 : Enabled
- U8
6657 0x1A01 1 Criticality :
0 : Information
1 : Warning
2 : Critical
- U8
6658 0x1A02 1 Acknowledgement method :
0 : None
1 : MODBUS only
2 : Logical input
- U8
6659 0x1A03 1 Input for ack
0 : Input 1
1 : Input 2
2 : Input 3
3 : Input 4
4 : Input 5
5 : Input 6
255 : Not used
- U8
6660 0x1A04 1 Output for report
0 : Output 1
1 : Output 2
2 : Output 3
3 : Output 4
4 : Output 5
5 : Output 6
255 : Not used
- U8
6661 0x1A05 1 Alarm Type
0 : None
1 : Net Rotation
20 : External Alarm
21 : I/O Connection Failure
22 : Controller Unavailable
23 : Load Not Supplied
9 : RTC Low Battery
24 : DC Aux. Supply Out Of Bounds
- U8
6662 0x1A06 1 Startup delay s / 2 U16
6663 0x1A07 1 Dropout delay s / 2 U16

ALM Sys Settings #2


Dec start address Hex start address Type Size Lock level Locked fcts Unlocked fcts
6664 0x1A08 Settings 8 USER READ READ | WRITE | WRITE_MANY

Dec address Hex address Words count Description Unit Data type
6664 0x1A08 1 Status :
0 : Disabled
1 : Enabled
- U8
6665 0x1A09 1 Criticality :
0 : Information
1 : Warning
2 : Critical
- U8
6666 0x1A0A 1 Acknowledgement method :
0 : None
1 : MODBUS only
2 : Logical input
- U8
6667 0x1A0B 1 Input for ack
0 : Input 1
1 : Input 2
2 : Input 3
3 : Input 4
4 : Input 5
5 : Input 6
255 : Not used
- U8
6668 0x1A0C 1 Output for report
0 : Output 1
1 : Output 2
2 : Output 3
3 : Output 4
4 : Output 5
5 : Output 6
255 : Not used
- U8
6669 0x1A0D 1 Alarm Type
0 : None
1 : Net Rotation
20 : External Alarm
21 : I/O Connection Failure
22 : Controller Unavailable
23 : Load Not Supplied
9 : RTC Low Battery
24 : DC Aux. Supply Out Of Bounds
- U8
6670 0x1A0E 1 Startup delay s / 2 U16
6671 0x1A0F 1 Dropout delay s / 2 U16

ALM Sys Settings #3


Dec start address Hex start address Type Size Lock level Locked fcts Unlocked fcts
6672 0x1A10 Settings 8 USER READ READ | WRITE | WRITE_MANY

Dec address Hex address Words count Description Unit Data type
6672 0x1A10 1 Status :
0 : Disabled
1 : Enabled
- U8
6673 0x1A11 1 Criticality :
0 : Information
1 : Warning
2 : Critical
- U8
6674 0x1A12 1 Acknowledgement method :
0 : None
1 : MODBUS only
2 : Logical input
- U8
6675 0x1A13 1 Input for ack
0 : Input 1
1 : Input 2
2 : Input 3
3 : Input 4
4 : Input 5
5 : Input 6
255 : Not used
- U8
6676 0x1A14 1 Output for report
0 : Output 1
1 : Output 2
2 : Output 3
3 : Output 4
4 : Output 5
5 : Output 6
255 : Not used
- U8
6677 0x1A15 1 Alarm Type
0 : None
1 : Net Rotation
20 : External Alarm
21 : I/O Connection Failure
22 : Controller Unavailable
23 : Load Not Supplied
9 : RTC Low Battery
24 : DC Aux. Supply Out Of Bounds
- U8
6678 0x1A16 1 Startup delay s / 2 U16
6679 0x1A17 1 Dropout delay s / 2 U16

ALM Sys Settings #4


Dec start address Hex start address Type Size Lock level Locked fcts Unlocked fcts
6680 0x1A18 Settings 8 USER READ READ | WRITE | WRITE_MANY

Dec address Hex address Words count Description Unit Data type
6680 0x1A18 1 Status :
0 : Disabled
1 : Enabled
- U8
6681 0x1A19 1 Criticality :
0 : Information
1 : Warning
2 : Critical
- U8
6682 0x1A1A 1 Acknowledgement method :
0 : None
1 : MODBUS only
2 : Logical input
- U8
6683 0x1A1B 1 Input for ack
0 : Input 1
1 : Input 2
2 : Input 3
3 : Input 4
4 : Input 5
5 : Input 6
255 : Not used
- U8
6684 0x1A1C 1 Output for report
0 : Output 1
1 : Output 2
2 : Output 3
3 : Output 4
4 : Output 5
5 : Output 6
255 : Not used
- U8
6685 0x1A1D 1 Alarm Type
0 : None
1 : Net Rotation
20 : External Alarm
21 : I/O Connection Failure
22 : Controller Unavailable
23 : Load Not Supplied
9 : RTC Low Battery
24 : DC Aux. Supply Out Of Bounds
- U8
6686 0x1A1E 1 Startup delay s / 2 U16
6687 0x1A1F 1 Dropout delay s / 2 U16

ALM Sys Settings #5


Dec start address Hex start address Type Size Lock level Locked fcts Unlocked fcts
6688 0x1A20 Settings 8 USER READ READ | WRITE | WRITE_MANY

Dec address Hex address Words count Description Unit Data type
6688 0x1A20 1 Status :
0 : Disabled
1 : Enabled
- U8
6689 0x1A21 1 Criticality :
0 : Information
1 : Warning
2 : Critical
- U8
6690 0x1A22 1 Acknowledgement method :
0 : None
1 : MODBUS only
2 : Logical input
- U8
6691 0x1A23 1 Input for ack
0 : Input 1
1 : Input 2
2 : Input 3
3 : Input 4
4 : Input 5
5 : Input 6
255 : Not used
- U8
6692 0x1A24 1 Output for report
0 : Output 1
1 : Output 2
2 : Output 3
3 : Output 4
4 : Output 5
5 : Output 6
255 : Not used
- U8
6693 0x1A25 1 Alarm Type
0 : None
1 : Net Rotation
20 : External Alarm
21 : I/O Connection Failure
22 : Controller Unavailable
23 : Load Not Supplied
9 : RTC Low Battery
24 : DC Aux. Supply Out Of Bounds
- U8
6694 0x1A26 1 Startup delay s / 2 U16
6695 0x1A27 1 Dropout delay s / 2 U16

ALM Sys Settings #6


Dec start address Hex start address Type Size Lock level Locked fcts Unlocked fcts
6696 0x1A28 Settings 8 USER READ READ | WRITE | WRITE_MANY

Dec address Hex address Words count Description Unit Data type
6696 0x1A28 1 Status :
0 : Disabled
1 : Enabled
- U8
6697 0x1A29 1 Criticality :
0 : Information
1 : Warning
2 : Critical
- U8
6698 0x1A2A 1 Acknowledgement method :
0 : None
1 : MODBUS only
2 : Logical input
- U8
6699 0x1A2B 1 Input for ack
0 : Input 1
1 : Input 2
2 : Input 3
3 : Input 4
4 : Input 5
5 : Input 6
255 : Not used
- U8
6700 0x1A2C 1 Output for report
0 : Output 1
1 : Output 2
2 : Output 3
3 : Output 4
4 : Output 5
5 : Output 6
255 : Not used
- U8
6701 0x1A2D 1 Alarm Type
0 : None
1 : Net Rotation
20 : External Alarm
21 : I/O Connection Failure
22 : Controller Unavailable
23 : Load Not Supplied
9 : RTC Low Battery
24 : DC Aux. Supply Out Of Bounds
- U8
6702 0x1A2E 1 Startup delay s / 2 U16
6703 0x1A2F 1 Dropout delay s / 2 U16



Maintenance informations


Maintenance_Table


Dec start address Hex start address Type Size Lock level Locked fcts Unlocked fcts
7680 0x1E00 Settings 36 USER READ READ | WRITE | WRITE_MANY

Dec address Hex address Words count Description Unit Data type
7680 0x1E00 16 Product Name - STRING_NORM
7696 0x1E10 16 Maintenance Phone Number - STRING_NORM
7712 0x1E20 2 Last Inspection Date - DATETIME
7714 0x1E22 1 Max Number of Password Attempts - U8
7715 0x1E23 1 Timeout after wrong password min U8



Commands


Commands


Dec start address Hex start address Type Size Lock level Locked fcts Unlocked fcts
21760 0x5500 Commands 5 USER NONE WRITE

Dec address Hex address Words count Description Unit Data type
21760 0x5500 1 Set Command / Alarm
0x01 : Set Manual Retransfer (By Keyboard )
0x02 : Clear TOF( By Keyboard )
0x03 : Set TOF ( By Keyboard )
0x04 : Set TON ( By Keyboard )
0x05 : Set EOF ( By input )
0x06 : Set EON ( By input )
0x07 : Clear EOF ( By input )
0x08 : Clear EON ( By input )
0x0A : Clear TON ( By Keyboard )
0x10 : Clear Faults ( By input )
0x15 : Set EST Reset (By keyboard)
- U8_HEX
21761 0x5501 1 Set Operating Mode
0x0010 : Auto Mode
0x0020 : Manu Mode
0x0040 : Inhibit Mode
- U16_HEX
21762 0x5502 1 Set Priority
0 : Network
1 : Source 1
2 : Source 2
- U8
21763 0x5503 1 Set Position
1 : Position in Zero
2 : Position in 1
3 : Position in 2
- U8
21764 0x5504 1 Set Genset Start Order
0 : GS1 start
1 : GS1 stop
2 : GS2 start
3 : GS2 stop
- U8

Network Autodetection


Dec start address Hex start address Type Size Lock level Locked fcts Unlocked fcts
12368 0x3050 Commands 1 USER NONE WRITE

Dec address Hex address Words count Description Unit Data type
12368 0x3050 1 Autodetect network
0 : No action
1 : Start Autodetection
- U8

ALM Acknowledgment


Dec start address Hex start address Type Size Lock level Locked fcts Unlocked fcts
6912 0x1B00 Commands 1 NONE WRITE WRITE

Dec address Hex address Words count Description Unit Data type
6912 0x1B00 1 Ack ID - U16

System


Action system ( Write Function only )


Dec start address Hex start address Type Size Lock level Locked fcts Unlocked fcts
57856 0xE200 Commands 1 NONE WRITE WRITE

Dec address Hex address Words count Description Unit Data type
57856 0xE200 1 Action :
0xA1 : Product Configuration storage
0xB2 : Product reset
0xE5 : Restore factory settings
- U8_HEX

Lock system


Dec start address Hex start address Type Size Lock level Locked fcts Unlocked fcts
58112 0xE300 Settings 2 NONE READ | WRITE | WRITE_MANY READ | WRITE | WRITE_MANY

Dec address Hex address Words count Description Unit Data type
58112 0xE300 1 Code to submit - U16
58113 0xE301 1 Delocker ID - U16

USB function ( Write Function only )


Dec start address Hex start address Type Size Lock level Locked fcts Unlocked fcts
57872 0xE210 Commands 1 NONE WRITE WRITE

Dec address Hex address Words count Description Unit Data type
57872 0xE210 1 USB function :
0x01 : DFU
0x02 : PCL
0x03 : Mass storage
- U8_HEX



Maintenance


Partial operating hours counter reset


Dec start address Hex start address Type Size Lock level Locked fcts Unlocked fcts
528 0x0210 Commands 1 USER NONE WRITE

Dec address Hex address Words count Description Unit Data type
528 0x0210 1 Reset command
0 : Reset
- U16

Reset counter and time meters


Dec start address Hex start address Type Size Lock level Locked fcts Unlocked fcts
23376 0x5B50 Commands 3 USER NONE WRITE

Dec address Hex address Words count Description Unit Data type
23376 0x5B50 1 Reset switch counters
0 : No action
1 : Reset
- U8
23377 0x5B51 1 Reset partial time on position counters
0 : No action
1 : Reset
- U8
23378 0x5B52 1 Reset Genset counters
0 : No action
1 : Reset
- U8

Reset histo


Dec start address Hex start address Type Size Lock level Locked fcts Unlocked fcts
544 0x0220 Commands 1 USER NONE WRITE

Dec address Hex address Words count Description Unit Data type
544 0x0220 1 Action
0 : No action
1 : Reset alarms history
4 : Reset events history
- U16


--X33F-LB08-0PZ4-60880f6c--